1. NOMENCLATURE Product Specification Variation Type Of Connection X : Not Applicable Electrical Characteristic F : 380-415V/3Ph/50Hz Model Type R : Heatpump Series B : B series Capacity 60 : 60,000 Btu/h Model Name RT :Rooftop Brand A : Acson...
2. FEATURES Package Unit Dubbed the “Plug and Play” equivalent in the air-conditioning industry, the single unit configuration allows free installation. No additional piping work is required as both the indoor and outdoor sides are pre-connected. Refrigerant is factory pre-charged to ensure clean and efficient operation. Structure &...
3. APPLICATION INFORMATION Operating Range Ensure the operating temperature is in allowable range. Cooling Caution : The use of your air conditioner outside the range of working Heating temperature and humidity can result in serious failure. Indoor temp. (°CDB)
Controllers Netware III (ART 60/90B/BR) Operating Mode Fan Speed Display Display Display the fan speed Display the current setting mode of operation (Auto/High/Medium/Low) Sleep Display Display the sleep / energy saving status Error Display Swing Display Display the air swing status Key Lock Display °C or °F...
Page 10
Operating Lamp On/Off - Starting operation: When the unit is off, press the ON/OFF button. The operation LED lights and the unit will be turned on. - Stopping operation: When the unit is on, press the ON/OFF button. The operation LED is extinguished and controls are turned off.
Page 11
Timer Active Display Current Time Display Key Lock – This feature protects the controls from being tempered with by children or authorized persons. – To activate, press MINUTE button three times consecutively, “KEY LOCK” symbol will appear on the LCD display.
Page 12
Sequential Controller (Model: ART 120/150/180B/BR) Sequential Controller Functions 1) Sequential Controller LCD Display A : Time display B : Error indication C : Compressor running display (up to 4 compressors) D : Key lock display E : Heat display (up to 2 heaters) F : Energy saving mode display G : Compressor defrost cycle display...
Page 13
e. Temperature Setting • To set the desired room temperature, press to increase or decrease the set temperature in the range of 16°C to 30°C. • Press both simultaneously to toggle between °C and °F setting. f. Time Setting Real time clock •...
Page 14
Error Error Faulty Indication Faulty Indication Code Code Room sensor short Compressor 2 de-ice Room sensor open Indoor coil sensor 1 short Indoor coil sensor 2 short 4) Installation Of LCD Remote Controller a) Accessories The following accessories are included. If any part is missing, contact your dealer immediately. 1 Remote controller 2 Wooden screw 4.1 x 16 (2 pieces) 3 Instruction manual...
Installation 1) Location for Installation Install the unit in a manner that prevents short cycling of condenser air back into the unit (as in the case of short circuit of discharge air). Allow sufficient space for maintenance around the unit. When two or more units are installed in a location, they must be positioned such that one unit will not be taking the discharge air from another unit.
Page 16
3) Duct Construction - These unis are equipped with supply and return air openings. Duct connection to the unit should be made with duct flanges and secured directly to the air openings with flexible duct connectors to avoid normal noise transmission. - To prevent air leakage, all duct seams should be sealed.
Page 17
6) Space Required Around Unit ART 60/90B/BR ( MINIMUM CLEARANCE ) MOTOR / BLOWER 1000 CONDENSER SERVICE INLET CONTROL BOX / AIR FILTER 1000 COMPRESSOR SERVICE SERVICE ( MINIMUM CLEARANCE ) ( MINIMUM CLEARANCE ) CONDENSER 1000 OUTLET (unit ; mm) All space value ;...
Page 18
ART 120/150B/BR MOTOR/ BLOWER 1000 CONDENSER SERVICE INLET 1000 CONDENSER INLET AIR FILTER 1000 SERVICE CONDENSER 2000 OUTLET (unit ; mm) All space value ; minimum clearance...
Page 19
7) Unit conversion In the case of converting to down flow unit, change according to the following steps. ART 60B/BR Step 1 Step 2 Remove the Pulley Belt Remove the side panel Remove screws at both sides Cover the horizontal supply opening with the blower support that detached from the blower Step 4...
Page 20
ART 90B/BR Step 1 Step 2 Remove the Pulley Belt Remove the side panel Remove screws at both sides The two side plates are srewed on the blower support as shown Cover the horizontal supply opening with the blower support that detached from the blower Step 4 Step 3...
Page 21
ART 120/150/180B/BR Step 1 Step 2 Detached motor base assy from blower Detached down-flow structure from blower Detached blower Remove the Pulley Belt Remove the side panel Detached the blower support The two down-flow structure are screwed to blower Step 4 Step 3 Cover the horizontal supply opening with the blower support that...
5. SELECTION PROCESS Drive Package Selection The following are the design requirements for ART120B unit: Model : ART120B Supply air Quantity = 4000 CFM External Static Pressure = 180 Pa Step 1: From the blower curve (at 4000 CFM) Standard operating system; Internal Static Pressure 100 Pa Step 2:...
Page 27
ART 120B/BR ART 120B(R) 1.1kW 0.75kW 0.55kW Standard Point Internal Static Pressure 2800 3200 3600 4000 4400 4800 5200 (CFM) 1320 1510 1700 1890 2075 2265 2455 (l/s) Air Flow (CFM) e l l e l l Type Diameter (mm) Bore (mm) Type Diameter (mm)
6. ENGINEERING & PHYSICAL DATA General Data - Cooling Only (R22) MODEL ART60B ART90B Btu/h 55000 85000 NOMINAL COOLING CAPACITY 16100 24900 NOMINAL TOTAL INPUT POWER (COOLING) 5680 8020 NOMINAL RUNNING CURRENT (COOLING) 15.4 POWER SOURCE V/Ph/Hz 380 ~ 415 / 3 / 50 REFRIGERANT TYPE / CONTROL R22 / CAP.
General Data - Cooling Only (R22) MODEL ART180B Btu/h 170000 NOMINAL COOLING CAPACITY 49800 NOMINAL TOTAL INPUT POWER (COOLING) 16550 33.6 NOMINAL RUNNING CURRENT (COOLING) POWER SOURCE V/Ph/Hz 380 ~ 415 / 3 / 50 REFRIGERANT TYPE / CONTROL R22 / CAP. TUBE 3.01 AIR DISCHARGE DUCTED...
General Data - Heat pump (R22) MODEL ART180BR Btu/h 170000 NOMINAL COOLING CAPACITY 49800 Btu/h 171000 NOMINAL HEATING CAPACITY 50200 NOMINAL TOTAL INPUT POWER (COOLING) 16550 NOMINAL TOTAL INPUT POWER (HEATING) 14550 NOMINAL RUNNING CURRENT (COOLING) 33.6 NOMINAL RUNNING CURRENT (HEATING) 32.1 POWER SOURCE V/Ph/Hz...
Components Data-Cooling Only (R22) MODEL ART60B ART90B TYPE CENTRIFUGAL QUANTITY MATERIAL GALVANISED STEEL GALVANISED STEEL EVAPORATOR DRIVE BELT DRIVE DIAMETER mm/in 254 / 10 381 / 15 LENGTH mm/in 203 / 8 381 / 15 TYPE INDUCTION MOTOR EVAPORATOR QUANTITY FAN MOTOR INDEX OF PROTECTION (IP) IP22...
Components Data-Cooling Only (R22) MODEL ART120B ART150B TYPE CENTRIFUGAL QUANTITY MATERIAL GALVANISED STEEL GALVANISED STEEL EVAPORATOR DRIVE BELT DRIVE DIAMETER mm/in 381 / 15 381 / 15 LENGTH mm/in 381 / 15 381 / 15 TYPE INDUCTION MOTOR EVAPORATOR QUANTITY FAN MOTOR INDEX OF PROTECTION (IP) IP22...
Components Data-Cooling Only (R22) MODEL ART180B TYPE CENTRIFUGAL QUANTITY MATERIAL GALVANISED STEEL EVAPORATOR DRIVE BELT DRIVE DIAMETER mm/in 381 / 15 LENGTH mm/in 381 / 15 TYPE INDUCTION MOTOR EVAPORATOR QUANTITY FAN MOTOR INDEX OF PROTECTION (IP) IP22 TYPE PROPELLER QUANTITY CONDENSER FAN MATERIAL...
Components Data-Heatpump (R22) MODEL ART60BR ART90BR TYPE CENTRIFUGAL QUANTITY GALVANISED STEEL MATERIAL GALVANISED STEEL EVAPORATOR DRIVE BELT DRIVE DIAMETER mm/in 254 / 10 381 / 15 LENGTH mm/in 203 / 8 381 / 15 TYPE INDUCTION MOTOR EVAPORATOR QUANTITY FAN MOTOR INDEX OF PROTECTION (IP) IP22 TYPE...
Components Data-Heatpump (R22) MODEL ART120BR ART150BR TYPE CENTRIFUGAL QUANTITY MATERIAL GALVANISED STEEL GALVANISED STEEL EVAPORATOR DRIVE BELT DRIVE DIAMETER mm/in 381 / 15 381 / 15 LENGTH mm/in 381 / 15 381 / 15 TYPE INDUCTION MOTOR EVAPORATOR QUANTITY FAN MOTOR INDEX OF PROTECTION (IP) IP22 TYPE...
Components Data-Heatpump (R22) MODEL ART180BR TYPE CENTRIFUGAL QUANTITY MATERIAL GALVANISED STEEL EVAPORATOR DRIVE BELT DRIVE DIAMETER mm/in 381 / 15 LENGTH mm/in 381 / 15 TYPE INDUCTION MOTOR EVAPORATOR QUANTITY FAN MOTOR INDEX OF PROTECTION (IP) IP22 TYPE PROPELLER QUANTITY CONDENSER FAN MATERIAL PLASTIC &...
Page 43
Safety Devices - Cooling Only (R22) MODEL ART60B ART90B TYPE HIGH PRESSURE SWITCH OPEN kPa/psi 2937 / 426 CLOSE kPa/psi 2413 / 350 TYPE SAFETY DEVICE LOW PRESSURE SWITCH OPEN kPa/psi 48 / 7 CLOSE kPa/psi 152 / 22 PHASE SEQUENCER DISCHARGE THERMOSTAT SETTING °C / °F 125 / 257...
Page 44
Safety Devices - Heatpump (R22) MODEL ART60BR ART90BR TYPE HIGH PRESSURE SWITCH OPEN kPa/psi 2937 / 426 CLOSE kPa/psi 2413 / 350 TYPE SAFETY DEVICE LOW PRESSURE SWITCH OPEN kPa/psi 48 / 7 CLOSE kPa/psi 152 / 22 PHASE SEQUENCER DISCHARGE THERMOSTAT SETTING °C / °F 125 / 257...
Power Table Cooling Mode Model: ART 60B/BR Outdoor DB, ° C Indoor WB Indoor DB ° C ° C PI (kW) PI (kW) PI (kW) PI (kW) PI (kW) PI (kW) 3.84 4.16 4.51 4.80 5.12 5.48 3.92 4.25 4.55 4.87 5.18 5.57...
Page 52
Cooling Mode ART 120B/BR Outdoor DB, ° C Indoor WB Indoor DB ° C ° C PI (kW) PI (kW) PI (kW) PI (kW) PI (kW) PI (kW) 7.13 7.87 8.66 9.36 10.11 10.97 7.28 8.04 8.75 9.49 10.21 11.11 7.38 8.14 8.89...
Page 53
Cooling Mode ART 180B/BR Outdoor DB, ° C Indoor WB Indoor DB ° C ° C PI (kW) PI (kW) PI (kW) PI (kW) PI (kW) PI (kW) 8.44 10.31 12.27 14.10 16.00 18.21 8.63 10.71 12.72 14.79 16.80 19.30 8.77 11.03 13.28...
Page 54
Heating Mode Model: ART 60BR Outdoor DB, ° C Indoor DB ° C PI (kW) PI (kW) PI (kW) PI (kW) PI (kW) 3.27 3.94 4.32 4.52 4.70 3.41 4.17 4.56 4.76 4.96 3.54 4.33 4.79 5.02 5.21 3.70 4.54 5.03 5.25 5.47...
Page 55
Heating Mode Model: ART 120BR Outdoor DB, ° C Indoor DB ° C PI (kW) PI (kW) PI (kW) PI (kW) PI (kW) 6.69 8.06 8.84 9.25 9.62 6.97 8.53 9.35 9.76 10.16 7.25 8.88 9.84 10.31 10.70 1660 7.57 9.32 10.32 10.78...
Page 56
Heating Mode Model: ART 180BR Outdoor DB, ° C Indoor DB ° C PI (kW) PI (kW) PI (kW) PI (kW) PI (kW) 10.94 13.18 14.45 15.13 15.73 11.34 13.73 14.96 15.59 16.20 11.73 14.07 15.44 16.11 16.67 2470 12.20 14.55 15.91 16.52...
9. ELECTRICAL DATA Electrical Data - Cooling Only (R22) MODEL ART60B ART90B INSULATION GRADE POWER SOURCE V/Ph/Hz 380 ~ 415 / 3 / 50 RATED INPUT POWER 1,000 EVAPORATOR MOTOR RATED RUNNING CURRENT 1.49 2.00 MOTOR OUTPUT 1,100 POLES INSULATION GRADE POWER SOURCE V/Ph/Hz 220 ~ 240 / 1 / 50...
Page 61
Electrical Data - Cooling Only (R22) MODEL ART180B INSULATION GRADE POWER SOURCE V/Ph/Hz 380 ~ 415 / 3 / 50 RATED INPUT POWER 2263 EVAPORATOR MOTOR RATED RUNNING CURRENT 4.42 MOTOR OUTPUT 3000 POLES INSULATION GRADE POWER SOURCE V/Ph/Hz 220 ~ 240 / 1 / 50 RATED INPUT POWER 1650 CONDENSER MOTOR 1...
Page 62
Electrical Data -Heatpump (R22) MODEL ART60BR ART90BR INSULATION GRADE POWER SOURCE V/Ph/Hz 380 ~ 415 / 3 / 50 RATED INPUT POWER 1,000 EVAPORATOR MOTOR RATED RUNNING CURRENT 1.49 2.00 MOTOR OUTPUT 1,100 POLES INSULATION GRADE POWER SOURCE V/Ph/Hz 220 ~ 240 / 1 / 50 RATED INPUT POWER 580 x 2 CONDENSER...
Page 63
Electrical Data -Heatpump (R22) MODEL ART180BR INSULATION GRADE POWER SOURCE V/Ph/Hz 380 ~ 415 / 3 / 50 RATED INPUT POWER 2263 EVAPORATOR MOTOR RATED RUNNING CURRENT 4.42 MOTOR OUTPUT 3000 POLES INSULATION GRADE POWER SOURCE V/Ph/Hz 220 ~ 240 / 1 / 50 RATED INPUT POWER 1650 CONDENSER MOTOR 1...
11. SERVICING & MAINTENANCE Service of the Filter Filter Position The filters are mounted in front of the indoor heat exchanger. - Remove any dust adhering to the filter by using a vacuum cleaner or wash in lukewarm water (below 40°C) with a neutral cleaning detergent. - Rinse the filter well and dry before placing it back onto the unit.
12. TROUBLESHOOTING When a malfunction of the air conditioner unit is detected, immediately switch off the main power supply- before proceeding with the following troubleshooting procedures.The following are common fault conditions and simple troubleshooting tips. If any other fault conditions whichare not listed occur, contact your nearest local dealer.
Page 74
Diagnostic Guidelines By means of pressure reading: Pressure Data Probable cause Circuit • High side 1. Overcharged with refrigerant. • Low side 2. Non-condensable gases in refrigerant circuit (e.g. air) 3. Obstructed air-intake / discharge. 4. Hot air short circuiting in outdoor unit. •...
Page 75
By means of diagnostic flow chart: Generally, there are two kinds of problems, i.e. starting failure and insufficient cooling/heating. “Starting failure” is caused by electrical defect while improper application or defects in refrigerant circuit causes “Insufficient cooling / heating”. i) Diagnosis of Electric Circuit : Faulty : Check : Cause...
Page 76
ii ) Diagnosis of Refrigerant Circuit / Application There might be some causes where the unit starts running but does not perform satisfactorily, i.e. insufficient cooling. Judgement could be made by measuring temperature difference of indoor unit’s intake and discharge air as well as running current.
Page 77
Insufficient Heating Indoor / Outdoor Coil Dirty Clean The Coil Restricted (Clogged) Air Circulation Clean The Filter Indoor Air Filter Dirty Fan Motor Malfunction Change Or Repair The Motor Obstruction At Air Inlet / Remove The Obstruction Outlet OfIndoor / Outdoor Unit Windows / Doors Wide Open High Heating Load Close The Windows / Doors...
13. EXPLODED VIEW AND PARTS LIST Model: ART 60B DESCRIPTION PART NUMBER PART NUMBER PILLAR, OD R01014091062 ASSY, BASE PAN R50014093062 ASSY, FRONT PANEL R50014093065 PLATE, BASE R01014091023 ASSY, DRAIN PAN R50014093068 PANEL, PARTITION R01014093072 SUPPORT, MOTOR R01014087794 PILLAR, CENTER L R01014091060 ASSY, BLOWER BASE R50014091086...
Page 79
PANEL, OD SERVICE R01014091064 HANDLING HANDLE SL/MSS R12014015328 RAIL FILTER COIL OD R01014091076 R01014059624 SUPPORT, ACCU & LIQUID RECEIVER PARTS NOT SHOWED IN DIAGRAM HANDSET,WIRED NETWARE3 ACSON R04089023827 1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE...
Page 80
ASSY, TUBING ITEM DESCRIPTION PART NUMBER ACCUMULATOR PA5083-11-7C R02119002010 FILTER DRIER, DML 084s DANFOSS R02169018759 COMPRESSOR, ASSY ZR72KC-TFD-522 COPELAND R50049004675 ASSY, ACCESS VALVE 1/4"X70mm R50054028348 ASSY, LOW PRESSURE SWITCH R50134048735 ASSY, HIGH PRESSURE SWITCH R50134062905 ASSY, CONTROLLER ITEM DESCRIPTION PART NUMBER BOX, CONTROL R01014091080 CONTROL MODULE...
Page 81
Model: ART 60BR DESCRIPTION PART NUMBER PART NUMBER ASSY, BASE PAN R50014093062 SUPPORT, MOTOR R01014087794 ASSY, BLOWER BASE R50014091086 PLATE, BASE R01014091023 PANEL, PARTITION R01014093072 COVER, DISCHARGE R01014091070 PILLAR, CENTER L R01014091060 COVER RETURN R01014091067 PILLAR, CENTER R R01014091061 BLOWER, AT10/8 NICOTRA R03029012648 AT01600312X1100 PANEL, PARTITION B...
Page 82
SUPPORT, ACCU & LIQUID RECEIVER R01014059624 HANDLING HANDLE SL/MSS R12014015328 PANEL, TOP 2 R01014091066 AIR FILTER, SARANET L746XW700mm R03084092112 PARTS NOT SHOWED IN DIAGRAM HANDSET,WIRED NETWARE3 ACSON R04089023827 1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE...
Page 84
Model: ART 90B DESCRIPTION PART NUMBER DESCRIPTION PART NUMBER DRAIN PAN, SECONDARY R01014094198 ASSY, STRUCTURE BASE FRONT R50014094739 ASSY, STRUCTURE BASE BACK R50014088634 PILLAR, RIGHT CENTER R01014087457 BELT, V SPZ 1450 R03059029411 ASSY, FRONT PANEL R50014094058 ASSY, BASE PANEL OUTDOOR R50014087503 ASSY, FILTER RAIL CENTER R50014087510...
Page 85
PULLEY, 1 SPZ 63/1108 R03049013762 HANDLING HANDLE R12014015328 PANEL, RETURN COVER R01014087487 PULLEY, BUSH 1108/24 R03044039695 PULLEY, BUSH 1610/25 R03044039698 PARTS NOT SHOWED IN DIAGRAM HANDSET,WIRED NETWARE3 ACSON R04089023827 1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE...
Page 87
Model: ART 90BR DESCRIPTION PART NUMBER DESCRIPTION PART NUMBER ASSY, STRUCTURE BASE FRONT R50014094739 PILLAR, RIGHT FRONT R01014087436 PILLAR, RIGHT BACK R01014087437 ASSY, STRUCTURE BASE BACK R50014088634 BELT, V SPZ 1450 R03059029411 PILLAR, LEFT BACK R01014089226 ASSY, BASE PANEL OUTDOOR R50014087503 DRAIN PAN, SECONDARY R01014094198...
Page 88
PANEL, SERVICE C/BOX R01014087485 BASE, MOTOR LOWER R01014094100 HANDLING HANDLE R12014015328 BASE, MOTOR UPPER R01014094101 PANEL, RETURN COVER R01014087487 PARTS NOT SHOWED IN DIAGRAM HANDSET,WIRED NETWARE3 ACSON R04089023827 1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE...
Page 90
Model: ART 120BR DESCRIPTION PART NUMBER PART NUMBER ASSY, BASE PAN MAIN RT120/150B(R) R50014096184 ASSY., PILLAR REAR CENTRE R50014099408 LEFT (P099804) ASSY, SEPARATOR (P096876) R50014096874 ASSY, SEPARATOR 1 (P093966) R50014099907 ASSY, SEPARATOR BIG R50014094518 ASSY, SEPARATOR 2 (P093967) R50014098417 ASSY., SEPARATOR OUTDOOR SMALL R50014099344 COVER, SEPARATOR BIG (P097347) R01014097304...
Page 91
ASSY, FILTER RAIL TOP R50014092303 ASSY, SUPPORT DOWN FLOW L R50014098461 ASSY, SUPPORT DOWN FLOW R R50014098462 ASSY, FILTER RAIL CENTRE R50014092293 HANDSET, WIRED SEQ LCD - ACSON R04089010790 BLOWER, SIROCCO AT 15-15SC R03029030445 NICOTRA SHEET, RUBBER 38X165mm R11024027389 ASSY, MOTOR SUPPORT...
Page 92
Model: ART 150BR DESCRIPTION PART NUMBER DESCRIPTION PART NUMBER ASSY, OUTDOOR COIL L (RT150BR) R50024091757 ASSY, BASE PAN MAIN R50014096184 RT150BR(REFER 96184) ASSY, OUTDOOR COIL R (RT150BR) R50024091758 ASSY, SEPARATOR (P096876) R50014096874 ATTACHMENT 1, SEPARATOR R01014092809 ASSY, SEPARATOR 2 (P093967) R50014098417 ASSY, INDOOR COIL RT150B(R) R50024091756...
Page 94
Model: ART 180BR DESCRIPTION PART NUMBER DESCRIPTION PART NUMBER ASSY, BASE PAN MAIN RT180B(R) R50014096461 ASSY., PILLAR REAR CENTRE R50014099408 LEFT (P099804) ASSY, DRAIN PAN (P092574) R50014092289 ASSY., PILLAR REAR CENTRE R50014099407 ASSY, SEPARATOR (P096876) R50014096874 RIGHT(P099805) ASSY, SEPARATOR 1 (P093966) R50014099907 ASSY, SEPARATOR 2 (P093967) R50014098417...
Page 95
SHEET, RUBBER R11024002528 MTGt5x38x180mm R331F133H02 ASSY, MOTOR SUPPORT R50014093843 ASSY, MOTOR BASE R50014093842 HANDSET, WIRED SEQ LCD R04089010790 - ACSON R03039031188 MOTOR,3.0KW 50HZ L 4HTD00885 HITACHI PULLEY, 2 SPZ 90/1610 R03044039715 ASSY, FILTER RAIL TOP R50014096527 PULLEY, BUSH 1610/28 R03044039699...
Page 96
While upmost care is taken in ensuring that all details in the publication are correct at time of going to press, we are constantly striving for improvement and therefore reserve the rights to alter model specifications and equipment without prior notice. Details of specifications and equipment are also subject to change to suit local conditions and requirements and not all models are available in every market.
Need help?
Do you have a question about the ART 60 B/BR and is the answer not in the manual?
Questions and answers