Troubleshooting - DeDietrich AWHP-2 MIV-3 User Manual

Alezio evolution reversible air / water "split inverter" heat pump
Table of Contents

Advertisement

8.2

Troubleshooting

Problems
Probable causes
The radiators are cold. The heating set point tem­
perature is too low.
The heating mode is deac­
tivated.
The radiator valves are
closed.
The heat pump is not op­
erating.
The water pressure is too
low (< 1 bar).
There is no domestic
The domestic hot water
hot water.
set point temperature is
too low.
The domestic hot water
mode is deactivated.
The energy-saving shower
head is restricting the wa­
ter flow.
The heat pump is not op­
erating.
The water pressure is too
low (< 1 bar).
Significant variations in
Insufficient water supply
domestic hot water
temperature
The heat pump does
The heating set point tem­
not work.
perature is too low.
The heat pump is not op­
erating.
The water pressure is too
low (< 1 bar).
An error code appears on
the display.
The water pressure is
Not enough water in the
too low (< 1 bar).
installation.
Water leak.
Clicking in the central
The central heating pipe
heating pipes
clamps are too tight.
.
There is air in the heating
pipes.
The water is circulating too
quickly in the central heat­
ing system.
Significant water leak
The pipes on the heat
underneath or in the
pump or the central heat­
vicinity of the heat
ing are damaged.
pump.
7611973 - v04 - 07032016
Corrections
Increase the value of parameter
ted, increase the temperature on it.
Activate the heating mode.
Open the valves on all radiators connected to the heating system.
Check that the heat pump is switched on.
Check the fuses and switches on the electrical installation.
Top up the installation with water.
Increase the value of parameter
Activate the domestic hot water mode.
Clean the shower head; replace it if necessary.
Check that the heat pump is switched on.
Check the fuses and switches on the electrical installation.
Top up the installation with water.
Check the water pressure in the installation.
Open the valve.
Increase the value of parameter
ted, increase the temperature on it.
Check that the heat pump is switched on.
Check the fuses and switches on the electrical installation.
Top up the system with water.
Correct the error if possible.
Top up the system with water.
Contact the installer.
Contact the installer.
It is essential that you vent any air in the domestic hot water tank, the
pipes and the taps to prevent the annoying noises likely to be produced
during heating or when drawing off water.
Contact the installer.
Contact the installer.
8 Troubleshooting
or, if a room thermostat is connec­
.
or, if a room thermostat is connec­
AWHP-2 MIV-3
31