Outdoor Unit: RXS09/12LVJU
Step
3
Heat up the brazed part
of the suction side and
disconnect it.
4
Lift the compressor up
and remove it.
289
Procedure
Suction side
Points
Note:
Never use a metal saw to cut
pipes because the sawdust may
enter the circuit.
When withdrawing the pipes, be
careful not to pinch them firmly
with pliers. The pipes may get
deformed.
Provide a protective sheet or a
steel plate so that the brazing
flame cannot influence
peripheries.
(R12032)
Be careful so as not to burn the
compressor terminals, the name
plate, the heat exchanger fins.
(R7254)
Removal Procedure