Ct Or Related Abnormality (24/30/36 Class Only) - Daikin FTXS30LVJU Service Manual

Inverter pair ftxs-l series fdxs-l series
Hide thumbs Also See for FTXS30LVJU:
Table of Contents

Advertisement

SiUS091133

4.22 CT or Related Abnormality (24/30/36 Class Only)

H8
Remote
Controller
Display
Method of
A CT or related error is detected by checking the compressor running frequency and CT-detected
Malfunction
input current.
Detection
 The compressor running frequency is more than A Hz, and the CT input current is less than B
Malfunction
Decision
Conditions
 If the error repeats, the system is shut down.
 Reset condition: Continuous run for about 60 minutes without any other error
 Defective power module
Supposed
 Broken or disconnected wiring
Causes
 Defective reactor
 Defective outdoor unit PCB
Service Diagnosis
A.
A (Hz)
B (A)
32
0.5
Troubleshooting
132