SiUS091133
Step
5
Remove the motor
mounting plate.
6
Remove the fan motor.
Removal Procedure
Procedure
Motor mounting plate
Indoor Unit: FTXS30/36LVJU
Points
 When reassembling the fan
motor and the fan rotor, provide
as much as 5 mm (0.2 inch) of
play between the side face of
the rotor and the bottom frame.
Side face of rotor
(R9564)
5 mm (0.2 inch)
Fan motor
(1) Insert the fan motor with approx.
5 mm (0.2 inch) left.
(2) Tighten the screw until it stops.
Then give the screw one more
turn.
(R9565)
(3) Rotate the fan rotor and confirm
the fan motor and the fan rotor
are installed appropriately.
(4) Tighten the screw completely if
appropriate.
(5) If not appropriate, go back to
(1).
Side face of
bottom frame
(R2808)
(R9582)