Daikin FTXS30LVJU Service Manual page 195

Inverter pair ftxs-l series fdxs-l series
Hide thumbs Also See for FTXS30LVJU:
Table of Contents

Advertisement

Indoor Unit: FTXS09/12LVJU
Step
2
Loosen the lock screw
and remove the fan
motor.
3
Press the bearing
ASSY from outside.
4
Remove the bearing.
185
Procedure
Lock screw
 When reassembling the fan
motor and the fan rotor, provide
as much as 5 mm (0.2 inch) of
play between the side face of
the rotor and the bottom frame.
Side face of rotor
Fan motor
(R8120)
(1) Insert the fan motor with approx.
5 mm (0.2 inch) left.
(2) Tighten the screw until it stops.
(R8121)
Then give the screw one more
turn.
(3) Rotate the fan rotor and confirm
the fan motor and the fan rotor
are installed appropriately.
(4) Tighten the screw completely if
appropriate.
(5) If not appropriate, go back to
(1).
(R8122)
SiUS091133
Points
Side face of
bottom frame
5 mm (0.2 inch)
(R2808)
(R9582)
Removal Procedure