10
z10 BC IMPP
High Ambient
Temperature
Low Ambient
Temperature
Low end humidity
High end humidity
Gaseous contamination
Particulate contamination 1. Room air must be filtered continuously using appropriate
Environment, Nonoperating:
Temperature
Rel Humidity
Maximum Dew Point
Gaseous contamination
Temperature
Rel Humidity
Wet Bulb
Shipping package
Temperature
Relative Humidity
Wet Bulb
Shipping package
Notes:
1. Maximum ambient temperature reduces 1
m (2953 ft).
2. ANSI/ISA-S71.04. 1985. "Environmental conditions for process measurement and
control systems: Airborne contaminants." Instrument Society of America, Research
Triangle Park, NC, 1985.
3. The deliquescent relative humidity of particulate contamination is the relative humidity at
which dust absorbs enough water to become wet and promote ionic conduction.
4. For ambient temperatures exceeding 25
system may increase significantly as the speeds of the air moving devices increase. See
"Acoustics" on page 99 for the declared acoustical noise emission levels for the system
under nominal temperature conditions of 23
o
3.6
F).
5. The machine should be in an environment that satisfies the operating environment
specifications for at least one day before it is powered on.
Environment, Operating:
Long-term recommended
4
27°C (80.6°F)
Long-term recommended
18° (64.4°F)
Long-term recommended
5.5°C (41.9°F) dew point
Long-term recommended
60% relative humidity and 15°C
(59°F) dew point
Class G1 as per ANSI/ISA S71.04–1985
filters.
2. The deliquescent relative humidity of the particulate
contamination shall be more than 80%
5
5°C (45°F) to 41°C (113°F)
8% - 80%
Less than 27°C (80.6°F)
Class G1 as per ANSI/ISA S71.04–1985
Environment, shipping:
-40°C (-40°F) to 60°C (140°F)
5% - 100% (no condensation)
Less than 29°C (84.2°F)
IBM-approved vapor barrier bag with desiccant
Environment, storage:
1°C (33.8°F) to 60°C (140°F)
5% -80% (no condensation)
Less than 29°C (84.2°F)
IBM-approved vapor barrier bag with desiccant
o
C (1.8
o
o
C (77
F), the acoustical noise levels of the
o
C plus or minus 2
Level 03c, May 2011
1, 5
Maximum ambient allowed
4
32°C (89.6°F)
Minimum ambient allowed
10° (50°F)
Minimum relative humidity
allowed
8%
Maximum relative humidity
allowed
80% relative humidity and 17°C
(62.6°F) dew point
2
3
2
o
F) for every 300 m (984 ft) over 900
o
o
C (73.4
F plus or minus

Advertisement

Table of Contents
loading