Wire Colors For Cut-End Cords - IBM Z10 Installation Manual

Business class
Hide thumbs Also See for Z10:
Table of Contents

Advertisement

|

Wire colors for cut-end cords

| | | |
| | |
| | |
| | |
| | |
| | |
48
z10 BC IMPP
Style AWG
System Location
FC 8991
World Trade
(200-415 VAC)
single-phase / 14 ft.
FC 8998
Type LSZH
World Trade
(200-480 VAC)
three-phase / 14 ft.
FC 8999
Type LSZH
World Trade
(200-415 VAC)
single-phase / 14 ft.
IBM continues to strongly recommend the use of a metal backbox (example shown below)
with our line cords using IEC-309 plugs.
Although in-line connectors and nonmetallic backboxes are available and compatible, they
are not recommended. These recommendations are based on the metal backbox providing:
Notes:
1. An added level of protection against a mis-wired phase and ground reversal.
2. In some cases, a metal backbox may be better for EMI mitigation.
You may choose not to use a metal backbox. In this case, please check your local code for
specific requirements.
Notes:
1. The customer must obtain the appropriate plugs and receptacles, based on existing
electrical codes, where those plugs and receptacles are not provided with the system.
These customer-provided plugs and receptacles should be installed by qualified
electricians.
2. The power cord set(s) provided are for use only with this product.
3. LSZH = low smoke, zero halogen
Wire Number
Color
Line 1
Brown
Line 2
Black
Line 3
Gray
Ground
Green/Yellow
Drain
clear or uninsulated
# of wires
Watertight Plug
Type DP-1
#10 AWG
(not provided - see Note
3 wire
2)
#10 AWG
(not provided - see Note
4 wire
2)
#10 AWG
(not provided - see Note
3 wire
2)
Description
Phase 1 (labeled "PH-1" on the wire insulation
Phase 2 (labeled "PH-2" on the wire insulation
Phase 3 (labeled "PH-3" on the wire insulation
Ground (labeled "GND" on the wire insulation
Cable shield - must be connected to GROUND
Level 03c, May 2011
Watertight Receptacle
(not specified - see Note
2)
(not specified - see Note
2)
(not specified - see Note
2)

Advertisement

Table of Contents
loading

Table of Contents