11.4.1
Monthly measures during stand-
still
Check that the screw compressor package/
chiller is constantly under overpressure. Check
the screw compressor package/chiller for leaks
using a leak detector.
Start the oil pump for approx. 5 minutes.
Manually rotate the compressor shaft (min. 10
revolutions).
11.4.2

Four weeks before restarting

Check the moisture content and ageing condition
of the refrigerating machine oil. Analyse the oil
for this purpose. Compare the results of the anal-
ysis with the values for fresh oil. We recommend
an oil change after 1 year (ammonia as refriger-
ant) (see Maintenance Instructions).
Check the insulation resistance of the drive
motors (see the operating manual for the electric
motor).
Switch on the oil pump.
Check the screw compressor package/chiller for
leakages.