9.3.1

Overview of the operating modes

Modes
Name
0
Service
1
Manual
+ Manual
2
Manual + Auto Manual Start/Stop via TP and full automatic local
3
Auto + Auto
4
Remote
+ HW (cont)
5
Remote
+ HW (pulse)
6
Remote
+ HW (loc.
SW)
7
Remote
+ HW (ext.
SW)
8
Remote
+ Net (cont)
9
Remote
+ Net (pulse)
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
Remark
Oil pump by itself
Compressor motor blocked
Manual control via Touch Panel (TP)
capacity control
Full automatic start/stop and local capacity control
Start/stop and capacity demand via digital contacts
(hardware) from a remote master controller. The GSC
TP derives from the continuous +/- signals the pulses
for capacity (indirect).
Start/stop and capacity demand via digital contacts
(hardware) from a remote master controller. The mas-
ter also generates the +/- signals as pulses for control-
ling the slide capacity directly.
Start/Stop from a remote master controller via digital
contacts (hardware). The GSC TP controls the output
depending on a local setpoint (TP) and from this set-
point also automatically switches the product ON/OFF.
Start/Stop from a remote master controller via digital
contacts (hardware). The GSC TP controls the output
depending on an external setpoint (analog input) and
from this setpoint also automatically switches the
product ON/OFF.
Start/stop and capacity demand via network from a
remote master controller. The GSC TP derives from
the continuous +/- signals the pulses for controlling the
capacity (indirect).
Start/stop and capacity demand via network from a
remote master controller. The master also generates
the +/- signals as pulses for controlling the capacity
directly.
Use, operation, control
Signal for ...
Start/Stop
Capacity +/-
Manual
Manual
Manual
Auto
Auto
Auto
External
External
continuous
External
External
pulses
External
Local
+ setpoint
Setpoint
deviation
External
Remote
+ setpoint
Setpoint
deviation
Network
Network
continuous
Network
Network
pulses
67