ControlMaster CM30 and CM50
Universal process controllers,
Number /
Icon
Message
212.018
NV Error Opt Bd 1
210.019
NV Error Opt Bd 2
208.020
NV Error
Comm Bd
206.021
NV Error
SW Key 1
204.022
NV Error
SW Key 2
202.023
NV Error
SW Key 3
Config Error
054.044
(052.045)
Tune Lp1 (2) Fail
062.042
(058.043)
Tune Lp1 (2) Noise
Table 7.1 Diagnostic Messages (Continued)
IM/CM/ED–EN Rev. B
1
1
/
and
/
DIN
4
2
Possible Cause
Failure of non-volatile memory on option board
1 or permanent corruption of its data.
Failure of non-volatile memory on option board
2 or permanent corruption of its data.
Failure of non-volatile memory on
communications board or permanent
corruption of its data.
Failure of non-volatile memory on Software key
1 or permanent corruption of its data.
Failure of non-volatile memory on Software key
2 or permanent corruption of its data.
Failure of non-volatile memory on Software key
3 or permanent corruption of its data.
The configuration contains a source that is no
longer present or valid.
Autotune has failed to complete its sequence
or has calculated values outside of its
permitted range.
Autotune has failed due to excessive process
or measurement noise.
7 Advanced Level
Suggested Action
Check calibration of AO2, AIN 3 and AIN4
(CM50 only).
Recalibrate If necessary. Acknowledge error. 
If problem persists contact local service
organization.
Check calibration of AO2, AIN 3 and AIN4. 
Recalibrate If necessary. Acknowledge error. 
If problem persists contact local service
organization.
Acknowledge error. Check communications
board is correctly identified by device. 
If problem persists contact local service
organization.
Acknowledge error. Check software key
functionality is enabled. 
If problem persists contact local service
organization.
Acknowledge error. Check software key
functionality is enabled. 
If problem persists contact local service
organization.
Acknowledge error. Check software key
functionality is enabled. 
If problem persists contact local service
organization.
Check invalid sources in diagnostics menu –
see Section 7.9, page 59. 
Check configuration, check I/O required for
configuration is present and correct any
illegal use of the invalid signal by changing
configuration or fitting additional option
cards.
Check process response. Consider if
Autotune dynamic setting should be
changed. Ensure process is stable and
repeat autotune. 
If problem persists tune the loop manually.
Check input wiring. Ensure process is stable
and repeat Autotune. 
If problem persists, tune the loop manually.