ControlMaster CM30 and CM50
Universal process controllers,
...Totalizer
Total DP's
Preset Count
Predet Count
Intermed'te Count
Wrap Enable
Reset Source
Reset Days
Reset Hour
50
1
1
/
and
/
DIN
4
2
Selects the number of decimal places displayed on the totalizer value.
The value the totalizer counts from and the value applied when the totalizer is reset.
The value at which the totalizer stops or wraps.
The value at which the intermediate count digital signal is activated. This can be used as
an alarm threshold to indicate when the Predet Count value is about to be reached.
If set to On, the total is reset automatically to the Preset Count value once the Predet
Count value is reached. The wrap Digital signal is activated for 1 second.
If set to Off the count stops when the Predet Count value is reached. The wrap Digital
signal is activated until the totalizer is reset.
The source required to reset the totalizer value. Selection is made on the rising edge.
Reset
Selects the day or days to reset the totalizer.
Selects the hour to reset the totalizer (the totalizer is always reset exactly on the hour).
7 Advanced Level