ControlMaster CM30 and CM50
Universal process controllers,
...Control / ...Loop 1 (2) Control / ...FeedForward
Mode
Off
Static Gain
Adaptive Gain
Source
Gain
Reset Adaptive FF
Adaptive Control
Adaptive Control alters the PID parameters automatically (see page 20) if the process changes. It monitors process
performance continuously and updates an internal process model. Based on this process model it calculates the
optimum control parameters and adapts the PID settings accordingly. Changes to the PID settings occur as soon as
the process dynamics change.
Warnings are provided if the control parameters are changed by more than a set amount. This is important to detect
conditions such as a blocked valve that could be interpreted by the adaptive controller as decreased process gain.
Run Autotune (see page 19) to set the initial values for the adaptive controller. In a few cases, Autotune may not work
well, for example in extremely noisy processes. In these cases, provide the adaptive controller with initial values of
Critical Period and Critical Gain by the user – see procedure below.
The adaptive controller uses the Autotune Dynamics setting to determine the optimum PID settings. If the process has
a long deadtime, or a noisy measuring signal, select Deadtime or PI at the Dynamics parameter – see page 20.
The adaptive controller does not work with Motorized Valve without Feedback output types – see Appendix Fig. D,
page 84.
Adaptive Control cannot be used if output tracking mode In Auto is set (see page 46) because the adaptive controller
receives false information.
42
1
1
/
and
/
DIN
4
2
Feedforward control is disabled.
Gain applied by FeedForward block is a fixed value set by the user.
Gain applied by the FeedForward block is set by the controller automatically. Adaptive
feedforward can be used even if Adaptive Control (see page 42) has not been enabled. For
Adaptive feedforward to operate, the system must first be tuned using Aututune – see page
19.
Adaptive Gain cannot be used with output tracking or with motorized valve without
feedback. FeedForward (see page 41) with static gain can be used with motorized valve
without feedback. Adaptive Gain cannot be used with pPI control – see page 39.
Used to select source of the disturbance variable (DV) – see Appendix A, page 79 for
description of sources.
Sets the gain to be used when in Static Gain mode.
In Adaptive Gain mode this value is set automatically by the controller.
If the controller is moved to another application, Adaptive feedforward must be reset.
7 Advanced Level
IM/CM/ED–EN Rev. B