ControlMaster CM30 and CM50
Universal process controllers,
...Device Setup / ...Basic Setup
Config Action
Continue
Hold
Inactive
Custom Template
Reset to Defaults
Security Setup
Basic Password
Advanced Password
Reset Passwords
Custom Config
Loop 1 (2) PV
Loop 1 (2) Split O/P
Loop 1 (2) Valve Mode
Loop 1 (2) Valve O/P
Loop 1 (2) Valve FB
Loop 1 (2) TP OP1
Loop 1 (2) TP OP2
Loop 1 (2) RSP
IM/CM/ED–EN Rev. B
1
1
/
and
/
DIN
4
2
The Config Action parameter is used to determine how the controller and controller
outputs behave when the Advanced level is entered – see page 24.
The controller continues to operate as in the operator level. Outputs continue to
operate as normal.
Puts the controller into Manual control mode.
When the Advanced level is exited, the controller returns to the pre-configuration mode
of operation.
Digital, relay and analog outputs are held at their value / state when configuration
mode is entered.
Puts the controller into Manual control mode.
When the Advanced level is exited, the controller returns to the pre-configuration mode
of operation.
Digital and relay outputs are turned off.
Analog outputs are set to 0 mA.
If this parameter is enabled, it enables the internal function blocks to be re-linked to
create custom configurations for special application requirements.
These sources are configured in Device Setup / Custom Config – see below.
Resets all configuration parameters to their default values.
3 Security access levels are provided, each protected by a password of up to 6
alphanumeric characters.
Note. Passwords Basic and Advanced level are not set at the factory and must be
entered by the end user(s).
Basic level provides access to the Basic level parameters – see Section 6, page 18.
Provides access to all configuration parameters – see Section 7, page 24.
Resets all passwords to factory values.
Sets the source for the process variable.
Sets the source for output to the split output function block.
Sets the valve operation mode, Feedback or Boundless – see page 21.
Sets the control input to the valve function block.
Sets the source for position feedback input.
Sets the source for control input to the time proportioning block for Output 1 – see
page 24.
Sets the source for control input to the time proportioning block for Output 2 see page
24.
Sets the source for the remote (external) setpoint.
7 Advanced Level