7.3. User PI control mode (P1-12 = 3)
P2-01
Digital input 1 (T2)
0..10,
Open: Stop (disable)
13..16,
Closed: Run (enable)
18
Open: Stop (disable)
11
Closed: Run (enable)
Open: Stop (disable)
12
Closed: Run (enable)
Open: Stop (disable)
17
Closed: Run (enable)
Open: Stop (disable)
19
Closed: Run (enable)
Open: Stop (disable)
20, 21
Closed: Run (enable)
Open: Stop (disable)
22
Closed: Run (enable)
Open: Stop (disable)
23
Closed: Run (enable)
When P3-05 = 1, Bipolar analog input controls PID setpoint. The feedback must then be connected to Analog input 2 and P3-10
NOTE
must be set to 0 (Default setting)
The external trip input only functions when the feedback source is the Bipolar analog input (P3-10 = 1)
Further information on configuring the PI controller for typical feedback applications; please refer to the Advanced User Guide.
7.4. Modbus Control Mode (P1-12 = 4)
P2-01
Digital input 1 (T2)
0..2, 4,
6..9,
Open: Stop (disable)
13..16,
Closed: Run (enable)
18
Open: Stop (disable)
3
Closed: Run (enable)
Open: Stop (disable)
5
Closed: Run (enable)
Open: Stop (disable)
10
Closed: Run (enable)
Open: Stop (disable)
11
Closed: Run (enable)
Open: Stop (disable)
12
Closed: Run (enable)
Open: Stop (disable)
17
Closed: Run (enable)
Open: Stop (disable)
19
Closed: Run (enable)
Open: Stop (disable)
20, 21
Closed: Run (enable)
Open: Stop (disable)
22
Closed: Run (enable)
Open: Stop (disable)
23
Closed: Run (enable)
24
Optidrive VTC – User Guide
Digital input 2 (T3)
No Function
Open : PID control
Closed : Preset speed 1
Open : Preset speed 1
Closed : PID control
Open : PID Control
Closed : Bipolar analog ref
Open : PID Control
Closed : Analog input 2 ref
Digital Output :
Drive Healthy = +24V
Digital Output :
Drive Healthy = +24V
Open : Normal Operation
Closed : Fire Mode
Digital input 2 (T3)
No Function
Open : Forward
Closed : Reverse
Open : Modbus Speed Ref
Closed : Preset Speed
Open : Master Speed Ref
Closed : Digital Speed Ref
Open : Master Speed Ref
Closed : Preset Speed 1
Open : Master Speed Ref
Closed : Bipolar Analog Ref
Open : Master Speed Ref
Closed : Bipolar Analog Ref
Open : Master Speed Ref
Closed : Analog Input 2 Ref
Digital Output :
Drive Healthy = +24V
Digital Output :
Drive Healthy = +24V
Open : Normal Operation
Closed : Fire Mode
www.invertek.co.uk
Digital input 3 / Analog input 2 (T4)
Analog input 2
External trip input :
Open: Trip,
Closed: No Trip
External trip input :
Open: Trip,
Closed: No Trip
Analog input 2
Analog input 2
Analog input 2
External trip input :
Open: Trip,
Closed: No Trip
No Function
Digital input 3 / Analog input 2 (T4)
No Function
Open: Modbus Speed Reference
Closed: Preset Speed 1 Reference
Digi Input 3
Bipolar Analog Input
Open
Open
Closed
Open
Open
Closed
Closed
Closed
External trip input :
Open: Trip,
Closed: No Trip
External trip input :
Open: Trip,
Closed: No Trip
External trip input :
Open: Trip,
Closed: No Trip
Open: Modbus / Analog Ref
Closed: Preset Speed 1
Analog Input 2
Open : Master Speed Ref
Closed : Preset Speed 1
External trip input :
Open: Trip,
Closed: No Trip
Open : Master Speed Ref
Closed : Preset Speed 1
Bipolar analog input (T6)
Bipolar analog input
Bipolar analog input
Bipolar analog input
Bipolar analog input
Bipolar analog input
Bipolar analog input
Bipolar analog input
Bipolar analog input
Bipolar analog input (T6)
Bipolar analog input
Bipolar analog input
Preset Speed
Preset Speed 1
Preset Speed 2
Preset Speed 3
Preset Speed 4
Bipolar analog input
Bipolar analog input
Bipolar analog input
Bipolar analog input
Bipolar analog input
Bipolar analog input
Bipolar analog input
Bipolar analog input