Micromaster 410 Specifications; Table 7-1 Micromaster 410 Performance Ratings - Siemens micromaster 410 Operating Instructions Manual

Table of Contents

Advertisement

Issue 04/02
7

MICROMASTER 410 Specifications

Table 7-1
MICROMASTER 410 Performance Ratings
Feature
Mains Operating Voltage &
Power Ranges
Input Frequency
Output frequency
Power Factor
Inverter Efficiency
Overload Capability
Inrush Current
Control Method
Pulse Frequency
Fixed Frequencies
Skip Frequencies
Setpoint Resolution
Output Frequency Resolution
Digital Inputs (PNP type)
Analog Input
Relay Output
Serial Interface
Electromagnetic Compatibility
Braking
Protection Level
Operation Temperature
Storage Temperature
Humidity
Operational Altitudes
Protection Features
Standards
CE Marked
Design/Manufacture
MICROMASTER 410
Operating Instructions
6SE6400-5EA00-0BP0
Specification
100 to 120 V ± 10% 1AC
200 to 240 V ± 10% 1AC
47 to 63 Hz
0 Hz - 650 Hz
≥ 0.95
96 to 97 %
Up to 150 % of rated output current for 60 seconds followed by 85 % of rated
output current for 240 seconds (cycle time 300 seconds)
Less than rated input current
Linear V/f ; Parabolic V/f; Flux Current Control (FCC); Multi-point V/f
2 kHz to 16 kHz (2 kHz steps)
3; programmable
1; programmable
0.01Hz digital, 0.01 Hz serial, 10 bit analogue
(motor potentiometer 0.1 Hz)
0.01 Hz digital, 0.01 Hz serial
3; freely programmable, non isolated, SIMATIC compatible
1; for setpoint (0 to 10 V, scalable or for use as 4
1; parameterizable, 30 V DC / 5 A (resistive), 250 V AC / 2 A (inductive)
RS-485, for operation with USS protocol
Variant with integrated EMC filter according to EN 61800-3
DC braking and Compound braking
IP20
-10 °C to +50 °C
-40 °C to +70 °C
95 % RH – non-condensing
Up to 1000 m above sea level without derating
Undervoltage, Overvoltage, Overload, Ground Faults, Short circuit, Stall
Prevention, Motor Overtemperature, Inverter Overtemperature Protection
UL, cUL, CE, C-tick
Conformity with EC Low Voltage Directive 73/23/EEC
filtered variants are also conform to Electromagnetic Compatibility Directive
89/336/EEC
In accordance with ISO 9001
7 MICROMASTER 410 Specifications
0.12 kW – 0.55 kW
0.12 kW – 0.75 kW
8 kHz Standard
th
digital input)
63

Hide quick links:

Advertisement

Table of Contents
loading