Issue 04/02
3.2.3
Changing the Line Supply Frequency
The supply frequency of the inverter
can be changed using either the
Operator Panel or by physically
cutting the Supply Frequency Link as
shown in Figure 3-4:
Cutting the supply link
The line supply frequency can be set
by cutting the supply link (see inset)
1. Ensure inverter is disconnected
from power supply.
2. Carefully cut the link with an
appropriate pair of wire-cutters.
3. Inverter is now set for 60 Hz.
The inverter can be set back to 50 Hz, by setting P0100 = 0.
Using the Operator Panel
The supply frequency can be set by the following parameters:
Ø Set P0100 = 0 (50 Hz) default
Ø Set P0100 = 1 (60 Hz)
3.2.4
Commissioning Overview with the optional Operator Panel
Prerequisites
Mechanical and electrical Installation are completed.
Quick Commissioning P0010 = 1
Further Commissioning via P0004 and P0003
An overview of the parameter structure is given in
For a detailed description of the parameter, see the
NOTE
We recommend the commissioning according this scheme. Nevertheless an expert
user is allowed to do the commissioning without the filter functions of P0004.
MICROMASTER 410
Operating Instructions
6SE6400-5EA00-0BP0
Power ON
See Section 3.2.4.2
Section 5.3
Parameter List.
Figure 3-4
Changing the Line Supply
Frequency
3 Commissioning
35