Battery settings
Com settings
9PX 1-3 KVA US_EN
Submenu
Available settings
Automatic battery
In ABM cycling mode :
test
[No test] [Every ABM cycle]
In constant charge mode:
[No test] [Every day] [Every week]
[Every month]
Low battery
[Capacity] [0%] ... [100%]
warning
[Runtime] [0min] ... [60min]
The alarm triggers when the set
percentage of battery capacity or
remaining back-up time is reached.
Restart bat. level
[0%] ... [100%]
If set, automatic restart will occur only
when percentage of battery charge is
reached.
Battery charge
[ABM cycling] [Constant charge]
mode
External battery
[Auto detection] [Manual EBM set.]
[Manual battery set.]
Deep Disch.
[Yes] [No]
protect.
If set to Yes, the UPS automatically
prevents battery from deep discharge
by adapting end of back-up time
voltage threshold.
Warranty void if set to No.
[ROO] [RPO] [DB9-4]
Input signals
Sets Input signals parameters
(function, delay, operation) through
external contact connectors or RS232
port.
ROO port:
- [Function]: [No] [ROO] [RPO]
[Building alarm] [Forced bypass] [On
generator] [Remote shutdown]
- [Delay]: [0s] ... [999s]
- [Active]: [Open] [Closed]
RPO port:
- [Function]: [No] [ROO] [RPO]
[Building alarm] [Forced bypass] [On
generator] [Remote shutdown]
- [Delay]: [0s] ... [999s]
- [Active]: [Open] [Closed]
DB9-4 port:
- [Function]: [No] [ROO] [RPO]
[Building alarm] [Forced bypass] [On
generator] [Remote shutdown]
- [Delay]: [0s] ... [999s]
- [Active]: [High] [Low]:
2. Presentation
Default settings
[Every ABM cycle]
[Every week]
[0%]
[3min]
[0%]
[ABM cycling]
[Auto detection]
Using standard EBM, UPS
detects automatically the
number of EBM connected
[Yes]
[No]
[0s]
[Closed]
[No]
[0s]
[Open]
[No]
[0s]
[High]