Chapter 7 : Troubleshooting - Delta HCH1850 User Manual

Precision cooling
Table of Contents

Advertisement

WARNING:
Unauthorized action may lead to major danger or equipment damage.
System Troubleshooting:
Abnormal
No.
phenomenon
1
The fans
cannot start.
2
The cooling unit
cannot start.
3
Forgot the
password?
4
The operation
noise is too high.
5
LCD display is
abnormal and does
not display.
6
The alarm condition
buzzer does not
beep.
InfraSuite RowCool Precision Cooling –
Chilled Water

Chapter 7 : Troubleshooting

Possible cause
The power supply
is abnormal.
The fans are abnormal.
The input voltage is
abnormal.
Forgot the user password
or admin password?
Foreign matter is attached
to the fans or the fans' ball
bearings are damaged.
The fan speed is too high.
There is foreign matter
or impurity in the pipeline.
The wiring is wrong.
The buzzer alarm function
is not enabled.
Elimination method
Make sure the input voltage is within the
permissible range, the circuit breaker or
switch is set at ON, and the cooling unit is
correctly grounded.
Make sure that each fan wiring is normal
and change the abnormal fans if necess-
ary.
Make sure the input voltage is within the
permissible range, the circuit breaker or
switch is set at ON, and the cooling unit is
correctly grounded.
Contact service personnel.
Clean and inspect the fans.
Check if the fans are running at full
speed. Adjust the set point or the fan
speed accordingly.
Inspect the Y-type filter of the external
piping and clean it if necessary.
Inspect if the wiring of the control panel
is correct or re-start the cooling unit if
necessary.
Use the control panel to enable the
buzzer alarm function. Path: Main Menu
50
.