Delta HCH1850 User Manual page 59

Precision cooling
Table of Contents

Advertisement

Appendix 1 :
Model
Max. Power Consumption
Air Volume
Rated Chilled Water Flow Rate
Pressure Drop
Drain Pump (Optional)
Display
Max. Return Air Temperature
Max. Water Inlet Temperature
Operational Audible Noise
Operating Temperature
Storage Temperature
Dimensions (Width x Depth x Height)
Net Weight
NOTE:
1. Refer to the rating label for the safety rating.
HCH1850 return air temperature: 35°C DB/ 19.8°C WB/ chilled water inlet temperature degree: 7.2°C/ chilled water
outlet temperature degree: 12.7°C.
HCH1870 return air temperature: 40.6°C DB/ 21.6°C WB/ chilled water inlet temperature degree: 7°C/ chilled water
outlet temperature degree: 15.8°C.
HCH1850 return air temperature 40.6°C DB/ 21.6°C WB/ chilled water inlet temperature: 7.2°C/ chilled water outlet
temperature: 13.8°C.
HCH1870 return air temperature 48.9°C DB/ 23.9°C WB/ chilled water inlet temperature: 7°C/ chilled water outlet
temperature: 15.4°C.
HCH1850
1.05 kW
25.2 kW
29 kW
4930m3/h
68.3 LPM
110 kPa
Flow rate: 5 l/h; Rated vertical lift: 5m
40
15
81.5 dBA @ 2900 CFM
4 ~ 40
30~85% RH, non-condensing
-15 ~ 65
(0 ~ 95% RH, non-condensing)
300 x 1090 x 2000 mm
185 kg
55
Appendix 1
HCH1870
2.41 kW
43.4 kW
59.1 kW
7500m3/h
80 LPM
98 kPa
50
15
88dB@4400CFM
4 ~ 50
300 x 1090 x 2000 mm
187 kg

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hch1870

Table of Contents