3.2

Space Reservation

In order to facilitate maintenance, operation,
and air circulation, please reserve a net
space around the equipment.
It is suggested to preserve 1200mm for the
front passage, 600mm for the rear passage
and at least 300mm above the cabinet for
pipe installation. If the pipeline adopts a lower
connection mode, the height of the raised
pipeline adopts an upper connection mode,
3.3

Handling

Handling Instructions
Before moving the equipment to the
installa-tion site, plan the route according
to the following instructions:
avoid collisions.
2. In the case of a slope on the handling route, its inclination must not be greater than 15
degrees so as to avoid toppling the cabinet.
3. The bottom casters are only suitable
for short distance movement. For long
distance movement, use a handling
device (such as Figure 3-2) so as to
avoid damage to the casters.
4. The casters are only suitable for moving
and moving of the unit on uneven ground,
which may damage the casters or even
result in toppling.
5. When moving the unit, pay attention to its height and center of gravity. At least two
people working together should handle the unit so as to guarantee safety.
InfraSuite RowCool Precision Cooling –
Chilled Water
Raised Floor
Common Floor
(Figure 3-2 : Forklift handling)
12
300
mm
1200
mm
300
mm
(Figure 3-1 : Space reservation)
600
mm