The program adopts a compensation method and adjusts the flow rate with the first (most
remote) cooling unit as a reference point. The process needs at least three people to work at
the same time. It is suggested keeping communication by handheld walkie talkie. The number
See the following procedures.
1
of the circuit.
2
Use the control panel to set all cooling units in the installation mode, (see 4.3 Operating
Temperature and Humidity) and the three-way ball valves will automatically fully open
(100%).
3
Fully open the balance valve of the return water end and the branch balance valves at
4
the balance valve cannot reach this value when fully opened, keep it at full opening, and
5
Fully open the branch balance valve of Unit 1, adjust the balance valve of the return
Make sure once again its branch balance valve is kept fully open.
6
7
person will observe the flow rate change of Unit 1, dynamically adjust the branch
8
Repeat the procedures
branch balance valves.
9
When all units are adjusted, record the opening of the balance valve of the return water
10
InfraSuite RowCool Precision Cooling –
Chilled Water
6
7
~
to adjust Units 4~6 and record the opening of the
32