Heat Pump Water Heater; 12 1.8 Operating Principle Of The Ventilation Heat Pump Water Heater - joule HEATBANK Operating And Installation Manual

Domestic hot water heater
Table of Contents

Advertisement

ENG
Installation and user manual
1.8 OPERATING PRINCIPLE OF THE VENTILATION

HEAT PUMP WATER HEATER

1.7
The Ventilation Heat Pump Water heater consists of an expansion
The Ventilation Heat Pump Water heater consists
valve (1), an air heat exchanger (2), a compressor (3) and a water heat
of an expansion valve (1), an air heat exchanger (2),
exchanger (4).
a compressor (3) and a water heat exchanger (4).
A refrigerant circulates in the closed system (5). In
A refrigerant circulates in the closed system (5). In the expansion valve,
the expansion valve, the pressure and temperature
the pressure and temperature of the refrigerant are lowered, which
of the refrigerant are lowered, which becomes
becomes vaporous. It extracts heat from the air (6) via the air heat
vaporous. It extracts heat from the air (6) via the air
exchanger . The vapour is then compressed
heat exchanger. The vapour is then compressed
by the compressor . This increases the pressure and the temperature
by the compressor. This increases the pressure
(7). The heat is transferred to the water via the water heat exchanger
and the temperature (7). The heat is transferred to
(8). And the cycle begins anew. It is therefore possible to heat water
the water via the water heat exchanger (8). And the
with a low temperature of 10 °C to domestic hot water with a tem-
cycle begins anew. It is therefore possible to heat
perature of 60 °C. This makes it possible to create four parts of energy
water with a low temperature of 10 ºC to domestic
(heat) from just one part of energy (electricity).
hot water with a temperature of 60 ºC. This makes
it possible to create four parts of energy (heat) from
Configurations which
just one part of energy (electricity).
are not allowed
Connection to the attic
or loft space .
The supply of air from
a heated room by the
VHW .
Connection to the me-
chanical ventilation .
Making of a housing
around the air outside or
a repulsion of fresh air
inside .
Connection to a ground
heat exchanger .
Not allowed
Make a ventilation connection with a dryer.
Install in dusty room.
Take air in which contains solvents and / or explosive substances.
Connect the VHW to an extractor fan wich drains oily and contami-
nated air .
Install the VHW in a room where there is a change of frost.
Install the VHW on top of the boiler.
Install in an atmosphere which is chlorinated (e.g. a swimming
pool) or fluorinated. • Install nearby sea areas or chemical plant
Dusty air intake.
12
10
OPERATING PRINCIPLE OF THE VENTILATION HEAT PUMP WATER HEATER
Consequences
When the insulation between the house and
the attic is not sufficient, through this con-
nection the loss of heat may increase . There
is also the possibility that a growing of mois-
ture will happen at the ceiling of the rooms
which are directly below the attic . There is
a chance that objects will fall or dust will be
drawn in by the VHW . This may reduce the
lifetime for the VHW .
The air which is drawn by the VHW is al-
ready warmed by another heating source
in the system . In this situation the great-
est benefit of the VHW (the transmitting of
'free' energy into heat) is not used.
he volume of air required by the VHW isn't
suitable (380 / 490 m/h) for the volume of
air in a mechanical ventilation (which is
100 m/u). Furthermore the vapor of grease
and dust in the ducts of the mechanical
ventilation can circulate through and that
may cause a shorter lifetime for the VHW .
This will cause a big loss in the coefficient
of performance and a strong cooling in the
room .
• Friction losses.
• Problems with the symmetrisation of
the two fans inside the ground heat ex-
changer .
• The evaporator will likely become
clogged .