Siemens BT300 Operator's Manual page 43

Bypass variable frequency drive
Hide thumbs Also See for BT300:
Table of Contents

Advertisement

Table 6: Expected Voltages, Conventional Bypass Diagnostic Test Points.
Test
Reference
Point
TP1
TP8
TP2
TP8
TP3
TP8
TP4
TP8
TP5
TP8
TP6
TP8
TP7
TP8
TP8
TP8
TP9
TP8
TP10
TP8
TP11
TP8
115 Vac (w/ M3)
0 Vac (No M3)
TP12
TP15
TP13
TP15
24 Vdc (On)
0 Vdc (Off)
TP14
TP15
24 Vdc (On)
0 Vdc (Off)
TP15
TP15
Siemens Industry, Inc.
Drive
Off
0 Vac
0 Vac
0 Vac
0 Vac
0 Vac
0 Vac
115 Vac
0 Vac
115 Vac
0 Vac
115 Vac
0 Vac
115 Vac
0 Vac
0 Vac
0 Vac
0 Vac
0 Vac
0 Vac
0 Vac
115 Vac (Test)
0 Vac (Off)
24 Vdc
24 Vdc
0 Vdc
0 Vdc
0 Vdc
0 Vdc
BT300 Bypass Operator's Manual
Conventional Bypass Diagnostic Board
Bypass
Essential Services Description
115 Vac
115 Vac
115 Vac
115 Vac
115 Vac
115 Vac
0 Vac
0 Vac
0 Vac
0 Vac
0 Vac
0 Vac
0 Vac
0 Vac
0 Vac
0 Vac
115 Vac
115 Vac (REM)
0 Vac (LOC)
115 Vac (REM)
0 Vac
0 Vac (LOC)
115 Vac (Test)
115 Vac (Test)
0 Vac (Off)
0 Vac (Off)
24 Vdc
24 Vdc
0 Vdc
0 Vdc
0 Vdc
0 Vdc
0 Vdc
0 Vdc
Troubleshooting
Point between ESR-B terminal 4
and M2A-B terminal 3.
M1 coil power.
M1 coil power.
Point between ESR-C terminal 7
and M1A-B terminal 3.
M2 coil power.
M2 coil power.
Point between BOD switch 'Drive'
position and ESR-C terminal 6.
Vac Neutral.
Point between BOD switch
'Bypass' position and LOC/REM
jumper.
Point between REM jumper and
RR-B terminal 3.
Point between Test Switch 'Off'
position and M3 coil (M3 coil
power).
24 Vdc from drive standard I/O
terminal 6.
Drive standard I/O terminal 9 (DI2
- Drive Contactor (M2) Interlock).
Drive standard I/O terminal 8 (DI1
- I/O Start) DI2 must be ON before
DI1 can be ON.
Vdc Common from drive standard
I/O terminal 13.
DPD01391
2016-08-05
43