Siemens BT300 Operator's Manual page 20

Bypass variable frequency drive
Hide thumbs Also See for BT300:
Table of Contents

Advertisement

Start-up Procedures
Startup Wizard (P1.19)
Step
Parameter/Question
13
Motor Nom Power (P3.1.1.6)
14
Min Frequency (P3.3.1)
15
Max Frequency (P3.3.2)
16
I/O Ctrl Ref (P3.3.3)
17
Accel Time (P3.4.2)
18
Decel Time (P3.4.3)
19
Ctrl Place Auto (P3.2.1)
20
Automatic Reset (P3.10.1)
21
Start Function (P3.2.4)
22
Stop Function (P3.2.5)
23
Motor Switch (P3.1.2.2)
24
Bypass Wizard (P1.21)
20
Siemens Industry, Inc.
Defines nominal motor power from motor nameplate data.
Minimum allowed frequency reference.
Maximum allowed frequency reference.
Selects location of frequency setpoint source when in I/O A control. In
the following list of possible settings, the main setpoint is selected:
1= Preset Freq 0
2 = Keypad Reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID 1 Reference
8 = Motor Potentiometer
Defines the time required to increase output frequency from 0 to Max
Frequency (P3.3.1).
Defines the time required to decrease output frequency from Max
Frequency (P3.3.1) to 0 frequency.
Start/Stop commands are given differently depending upon the control
place. This parameter defines whether the Start/Stop command is
controlled by digital inputs as defined in Control Signal 1 A (P3.5.1.1)
and Control Signal 2 A (P3.5.1.2) in accordance with the I/O A
Start/Stop Logic (P3.2.6) or if the Start/Stop command is controlled by
the Fieldbus that is in use.
Settings:
0 = I/O Control (control is from the physical I/O, PID control, or time
channels)
1 = Fieldbus (control is from the configured fieldbus found in Ethernet
or RS-485 settings).
Determines if the Automatic Reset feature can be used.
Defines the start function of the drive.
0 = Ramping Start
1 = Flying Start
Defines the stop function of the drive.
0 = Coast to Stop
1 = Ramping Stop
Prevents the drive from tripping when a motor switch is located
between the drive and motor.
0 = No
1 = Yes
Enable parameter for the Bypass Wizard. This wizard can be activated
during the Startup Wizard.
The Startup Wizard is now complete.
BT300 Bypass Operator's Manual
Settings
DPD01391
2016-08-05