Siemens BT300 Operator's Manual page 40

Bypass variable frequency drive
Hide thumbs Also See for BT300:
Table of Contents

Advertisement

Troubleshooting
Electronic Bypass Diagnostic Board
Table 5: Expected Voltages, Electronic Bypass Diagnostic Test Points.
Test
Point
Reference
TP1
TP8
TP2
TP8
TP3
TP8
TP4
TP8
TP5
TP8
TP6
TP8
TP7
TP8
TP8
TP8
TP9
TP8
TP10
TP8
TP11
TP8
TP12
TP15
TP13
TP15
TP14
TP15
TP15
TP15
40
Siemens Industry, Inc.
Expected Voltage
Drive
Off
115 Vac
115 Vac
0 Vac
115 Vac
0 Vac
0 Vac
115 Vac
115 Vac
115 Vac
115 Vac
115 Vac
0 Vac
0 Vac
0 Vac
BT300 Bypass Operator's Manual
Bypass/
Essential
Description
Services
115 Vac
Point between OL1 term 96 and M2A-B terminal 3.
115 Vac
Point between M2A-B terminal 2 and Drive OPT-B5 card
terminal 22.
115 Vac
Drive OPT-B5 card terminal 23 (M1 coil power).
115 Vac
Point between OL1 terminal 96 and M1A-B terminal 3.
0 Vac
Point between M1A-B terminal M2 and Drive OPT-B5 card
terminal 25.
0 Vac
Drive OPT-B5 card terminal 26 (M2 coil power).
Not used.
0 Vac
Vac Neutral.
Not used.
Not used.
Not used.
Not used.
Not used.
Not used.
Not used.
DPD01391
2016-08-05