TECO speecon 7200ma Instruction Manual page 21

Table of Contents

Advertisement

Input Voltage Class
MODEL
Basic Control
Function
Extra Function
Stall Prevention
Instantaneous
Overcurrent
Motor Overload
Protection
Inverter Overload
Protection
Overvoltage
Undervoltage
Momentary Power Loss
Ride-Through time
Overheat Protection
Grounding Protection
Charge Indication (LED)
Mechanical Construction
Cooling
Weight (kg)
Application Site
Ambient Temperature
Storage Temperature
Ambient Humidity
Height, Vibration
Communication Function
EMI
EMC Compatibility
Option
*1 : The standard type ( JNTMBGBB□□□□ JK/AZ - - -) use self cooling. Its weight is 4.12kg.
The compact type ( JNTMBGBB□□□□ JK/AZ S - -) use forced cooling. Its weight is 2.29kg.
220V CLASS
1 /3-Phase
JNTMBGBB□□□□JK
0001 0002 0003 0005 7R50 0010 0015 0020 0001 0002 0003 0005 7R50 0010 0015 0020
Restart After Momentary Power Loss, PID Control, Auto Torque
Boost, Slip Compensation, RS_485 Communication, Speed
Feedback Control, Simple PLC function, 2 Analog Output Port
Cumulative Power on & Operation Hour memory, Energy Saving,
Up/Down Operation, 4 Different sets of Fault Status Record
(Including Latest one), MODBUS Communication, Multiple-Pulse
Output Ports, etc.
During Acceleration/Deceleration and constant Speed Running
(Current Level Can Be Selected During Acceleration and Constant
Speed Running. During Deceleration, Stall Prevention Can Be
Enabled or Disabled)
Stopped if above 200% Rated Current
Electronic Overload Curve Protection
Stopped if above 150% Rated Current for 1 Min.
Stop if VDC≧410V (220 Class) or VDC≧820V (440 Class)
Stop if VDC≦200V (220 Class) or VDC≦400V (440 Class)
Protection by DC Current Sensor
Lit when the DC Bus Voltage Above 50V
Enclosed, Wall-Mounted Type (NEMA-1)
*1
Forced
Forced
*1
*1
4.25 4.25 5.73 5.73 10.5 10.5
2.29
2.29
Indoor (No Corrosive Gas And Dust Present)
Below 90%RH (Non-Condensing)
Below 1000M, 5.9m/S
RS-485 Installed (MODBUS Protocol)
Meet EN50081-2 (1994) With Specified EMI Filter
19
3-Phase
JNTMBGBB□□□□AZ
≧15ms, stop otherwise
Protected by Thermistor
Forced
*1
2.29
-10ºC ~ +40ºC (Not Frozen)
-20ºC ~ +60ºC
2
(0.6G), (JISC0911 Standard)
Meet Pr EN 50082-2
PROFIBUS Card
440V CLASS
3 Phase
*1
Forced
*1
4.25 4.25 5.73 5.73 10.5 10.5
2.29

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the speecon 7200ma and is the answer not in the manual?

Table of Contents