Part of the CE-typical drive System on mounting plate
c o n n e c t i o n
b e t w e e n
m o u n t i n g p l a t e a n d
C a b l e s b e t w e e n m a i n s f i l t e r
C a b l e s b e t w e e n m a i n s f i l t e r
a n d c o n t r o l l e r l o n g e r t h a n 0 . 3 m
a n d c o n t r o l l e r l o n g e r t h a n 0 . 3 m
must be screened
P E c o n n e c t i o n
4.2.4 Switching on the motor side
Switching on the motor side is permissible for an emergency stop
as weil as during normal Operation.
Please note that when switched with the controller enabled, this
may Cause the fault message OCl (shott circuitiearth fault). For
long motor cables, the fault current on the interfering cable
capacitances tan become so large that the short circuit monitoring
of the device is triggered. In these cases, a motor filter is necessary
to reduce the fault currents (See page 45).
P a i n t - f r e e b a r e m e t a l
P a i n t - f r e e b a r e m e t a l
, contact surfaces
S c r e e n e d
c o n t r o l c a b l e s
S c r e e n e d m o t o r c a b l e ,
connect Screen
to PE
a l s o a t t h e m o t o r s i d e ,
l a r g e cross-section
c o n t a c t t o t h e m o t o r
h o u s i n g r e q u i r e d
27