Lennox EL296DFV Installation Instructions Manual page 17

Elite series gas furnace downflow air discharge
Hide thumbs Also See for EL296DFV:
Table of Contents

Advertisement

2 - When furnace is installed in a residence where unit is
shut down for an extended period of time, such as a
vacation home, make provisions for draining conden­
sate collection trap and lines.
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a
venting system commonly run with separate gas ap­
pliances, the venting system is likely to be too large to
properly vent the remaining attached appliances.
Conduct the following test while each appliance is operat­
ing and the other appliances (which are not operating) re­
main connected to the common venting system. If the
venting system has been installed improperly, you must
correct the system as indicated in the general venting re­
quirements section.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon mon­
oxide poisoning or death.
The following steps shall be followed for each ap­
pliance connected to the venting system being
placed into operation, while all other appliances
connected to the venting system are not in
operation:
1 - Seal any unused openings in the common venting sys­
tem.
2 - Inspect the venting system for proper size and horizontal
pitch. Determine that there is no blockage, restriction,
leakage, corrosion, or other deficiencies which could
cause an unsafe condition.
3 - Close all building doors and windows and all doors be­
tween the space in which the appliances remaining
connected to the common venting system are located
and other spaces of the building. Turn on clothes dry­
ers and any appliances not connected to the common
venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they will oper­
ate at maximum speed. Do not operate a summer ex­
haust fan. Close fireplace dampers.
4 - Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so that
the appliance operates continuously.
5 - After the main burner has operated for 5 minutes, test
for leaks of flue gases at the draft hood relief opening.
Use the flame of a match or candle.
6 - After determining that each appliance connected to the
common venting system is venting properly, (step 3)
return all doors, widows, exhaust fans, fireplace damp­
ers, and any other gas-burning appliances to their pre­
vious mode of operation.
7 - If a venting problem is found during any of the preced­
ing tests, the common venting system must be modi­
fied to correct the problem.
Resize the common venting system to the minimum
vent pipe size determined by using the appropriate
tables in Appendix G. (These are in the current stan­
dards of the National Fuel Gas Code ANSI Z223.1.
Exhaust Piping (Figures 25 and 26)
Route piping to outside of structure. Continue with installa­
tion following instructions given in piping termination sec­
tion.
Carbon Monoxide Poisoning Hazard
Cutting or altering exhaust or air intake pipes, which
are located in the blower compartment, could result
in Carbon Monoxide Poisoning or Death.
Do not discharge exhaust into an existing stack or
stack that also serves another gas appliance. If verti­
cal discharge through an existing unused stack is re­
quired, insert PVC pipe inside the stack until the end
is even with the top or outlet end of the metal stack.
The exhaust vent pipe operates under positive pres­
sure and must be completely sealed to prevent leak­
age of combustion products into the living space.
Page 17
WARNING
CAUTION
CAUTION

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents