Lennox EL296DFV Installation Instructions Manual page 10

Elite series gas furnace downflow air discharge
Hide thumbs Also See for EL296DFV:
Table of Contents

Advertisement

WARNING
Improper installation of the furnace can result in per­
sonal injury or death. Combustion and flue products
must never be allowed to enter the return air system
or air in the living space. Use sheet metal screws and
joint tape to seal return air system to furnace.
In platform installations with furnace return, the fur­
nace should be sealed airtight to the return air ple­
num. A door must never be used as a portion of the
return air duct system. The base must provide a
stable support and an airtight seal to the furnace. Al­
low absolutely no sagging, cracks, gaps, etc.
For no reason should return and supply air duct sys­
tems ever be connected to or from other heating de­
vices such as a fireplace or stove, etc. Fire, explo­
sion, carbon monoxide poisoning, personal injury
and/or property damage could result.
The unit may be installed three ways in downflow applica­
tions: on non-combustible flooring, on combustible flooring
using an additive base, or on a reverse-flow cooling coil
cabinet. Do not drag the unit across the floor in the
downflow position. Floor and furnace flange damage
will result.
Refer to figure 13 for clearances in downflow applica­
tions.
Downflow Application Installation Clearances
Left Side
Bottom
Top
*Front
Back
Sides
Vent
Floor
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
†Allow proper clearances to accommodate condensate trap and
vent pipe installation.
‡The furnace may be installed on a combustible wood floor if an op­
tional additive base is installed between the furnace and the com­
bustible floor.
FIGURE 13
Top
Right Side
0
0
0
0†
0
NC‡
Installation on Non-Combustible Flooring Figure 14
1 - Cut floor opening keeping in mind clearances listed on
unit rating plate. Also keep in mind gas supply connec­
tions, electrical supply, flue and air intake connections
and sufficient installation and servicing clearances.
See table 1 for correct floor opening size.
2 - Flange warm air plenum and lower the plenum into the
opening.
3 - Set the unit over the plenum and seal the plenum to
the unit.
4 - Ensure that the seal is adequate.
NON-COMBUSTIBLE FLOOR OPENING SIZE
Cabinet Width
B Cabinet (17.5")
19 - 3/4
C Cabinet (21")
19 - 3/4
NOTE - Floor opening dimensions listed are 1/4 inch (6 mm) larger than
the unit opening. See dimension drawing on page 2.
FURNACE
PROPERLY
SIZED FLOOR
OPENING
Installation on Combustible Flooring Figure 15
1 - When unit is installed on a combustible floor, a down­
flow combustible flooring base must be installed be­
tween the furnace and the floor. The base must be or­
dered separately. See table 2 for opening size to cut in
floor.
The furnace and combustible flooring base shall not
be installed directly on carpeting, tile, or other com­
bustible material other than wood flooring.
Page 10
TABLE 1
Front to Rear
Side to Side
in.
mm
in.
502
16 - 5/8
502
20-1/8
SUPPLY AIR
PLENUM
FIGURE 14
CAUTION
mm
422
511

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents