PROGRAMMING A REPLACEMENT CONTROL BOARD

Indigo™ replacement control boards require the Model
number to be entered to activate the appropriate look up
tables for operation and diagnostic. This can be done two
different ways, USB Setup or Manual Setup.
USB Setup - Applicable when the control board is
operational and has a mechanical issue such as a sticking
relay. The asset data is transferred to the replacement
control board from the faulty control board. Refer to page
97 "Exporting Data To A Flash Drive" before installing the
replacement board.
Manual Setup - Applicable when the control board is
non-operational or data from the faulty board is suspect.
Install replacement control board and reapply power.
G series (blue) control boards will go directly to the
Replacement Control Board screen and pause for
input - Select either "Manual" or "USB" setup option.
E series (green) control boards require navigation to
the Replacement Control Board (Repl Cntl Bd) screen.
1. Press the Menu button.
2. Press the Down arrow until Service is highlighted,
then press the Checkmark.
3. Scroll down to Replacement Control Board and press
the Checkmark.
4. Select "Manual Setup" and press the Checkmark.
Verify the date correctly auto populates.
Yes - Go to step 5
No - Press the right arrow to activate the cursor, then
use up/down arrows to enter the correct date.
Part Number STH025 11/16