Manitowoc indigo series Technician's Handbook page 142

Air/water/remote condenser ice machine
Hide thumbs Also See for indigo series:
Table of Contents

Advertisement

Analyzing Discharge Pressure in the Freeze Cycle
1. Determine the ice machine operating conditions:
Air temp. entering condenser
Air temp. around ice machine
Water temp. entering sump trough
2. Refer to Operating Pressure table (starting on page
223) for ice machine being checked.
Use the operating conditions determined in step 1 to
find the published normal discharge pressures.
Freeze Cycle ______
Harvest Cycle ______
3. Perform an actual discharge pressure check.
1 Minute into the
Freeze Cycle
Middle of Freeze Cycle
End of Freeze Cycle
4. Compare the actual discharge pressure (step 3) with
the published discharge pressure (step 2).
The discharge pressure is normal when the actual
pressure falls within the published pressure range
for the ice machine's operating conditions. It is
normal for the discharge pressure to be higher at
the beginning of the Freeze cycle (when load is
greatest), then drop throughout the Freeze cycle.
142
______
______
Freeze Cycle
psig (kPa)
__________
__________
__________
Part Number STH025 11/16