Emc And Environmental Type Tests - Siemens RUGGEDCOM i802 Installation Manual

Table of Contents

Advertisement

Chapter 6
Certification
Agency
CSA
Section 6.3

EMC and Environmental Type Tests

The RUGGEDCOM i802 has passed the following EMC and environmental tests.
IEC 61850-3 Type Tests
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEEE 1613 EMC Immunity Type Tests
ESD
22
Standards
CSA C22.2 No. 142, CSA
C22.2 No. 213, UL No. 916,
ANSI/ISA-12.12.01-2007
CSA C22.2 No. 60950-1-03,
UL 60950-1, UL 508
Description
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced (Conducted) RFI
Magnetic Field
Voltage Dips
Damped Oscillatory
Mains Frequency Voltage
Ripple on DC Power Supply
Description
Enclosure Contact
Comments
Hazardous Location
Safety
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
DC Power ports
Signal ports
DC Power ports
Signal ports
DC Power ports
Earth ground ports
Enclosure ports
DC Power ports
Signal ports
DC Power ports
Signal ports
DC Power ports
DC Power ports
Test Levels
EMC and Environmental Type Tests
RUGGEDCOM i802
Installation Guide
Status
Approved
Approved
Test Levels
± 4 kV
± 8 kV
20 V/m
± 4 kV @ 5 kHz
± 2 kV @ 5 kHz
± 1 kV line-to-earth
± 0.5 kV line-to-earth/line
10 V
30 A/m
30% reduction for 0.5 period
2.5 kV common, 1 kV
differential mode @ 1 MHz
2.5 kV common, 1 kV
differential mode @ 1 MHz
10 V Continuous, 100 V for 1 s
10 V Continuous, 100 V for 1 s
10%
± 4 kV