FACP Configuration Templates
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3 (Water-
flow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull Station) will
operate Alarm Relay
Trouble Relay - any system trouble will activate the Trouble Relay
Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay
Device Installation Example for Template 2
Output Circuit #1
Alarm NAC
Output Circuit #2
1
Waterflow NAC
Notes:
1.
Waterflow Delay is programmed for 60 seconds.
2.
All End-of-Line Resistors, illustrated in this example, are 4.7KΩ, ˝ watt (PN: 71252).
3.
All devices are connected as Class B circuits. For details on connecting as Class A circuits,
refer to "CAC-5X Class A Converter Module" on page 29.
100
Input Circuit #1
2-Wire Smoke
Input Circuit #2
Fire (Heats)
Input Circuit #3
1
Waterflow
Input Circuit #4
Manual Release
Input Circuit #5
Pull Station
Template 2: Single Hazard - Cross-Zone With Manual Release
Output Circuit #4
Supervisory Bell
NAC
Output
Circuit #3
Release
Solenoid 1
PDRP-2001 Series Manual — P/N 53043:E4 7/28/2016
Input Circuit #6
Supervisory