Technical Data - Siemens SIMEAS P 7KG7100 Operating Instructions Manual

Power meter
Table of Contents

Advertisement

Available languages

Available languages

2.9

Technical Data

Input signals
Max. system voltage
Overload
Frequency of fundamental
component
Frequency range f
Waveform
AC current inputs
Input current I
i
Continuous overload
Surge withstand capability
Power consumption per phase 83 µVA at 1 A ; 2.1 mVA at 5 A
AC voltage inputs
Input voltage U
I
Continuous overload capacity
Surge withstand capability
Input resistance (L - N)
Power consumption per phase 120 mW (U
Binary inputs
Max. input voltage
Current consumption for high
level
Threshold voltage low
Threshold voltage high
Signal delay
Analog inputs
Measuring range
Input range
Input resistance
Accuracy
Only for connection to AC systems
Y 400 /∆ 690 V
20%
40 ... 65 Hz
+/- 5 Hz, min. > 30% U
i
Sinusoidal or distorted up to the
21st harmonic
I
I
1 A; 5 A
10 A
100 A for 1s
U
I
100/110 V; 190 V; 400 V; 690 V (L-L)
1.5 x U
2.0 x U
2.663 MΩ
(optional, only 7KG7610)
300 V DC
1.8 mA
≤10 V
≥19 V
max. 3 ms
(optional, only 7KG7610)
0 to 20 mA DC
0 to 24 mA DC
50 Ω ± 0.1%
0.5% of the measuring range limit
65
3 current inputs
3 voltage inputs
I
I
= 400 V)
LE
IN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents