21
Cycle Time
t.c.
Cycle time for time-proportioning output (10/15sec for
PID contactors, 1 sec for PID on SSR or value declared by
manufacturer for motorised valves)
0.1-300.0 sec. > Default: 10.0.
For motorised valve min. time is 1.0 sec
22
Output Power Limit
o.po.L.
limit of output power %.
10-100 % > Default: 100
23
Alarm
aL. 1
operating mode for Alarm 1. Intervention of the alarm is
associated to AL1.
Disabled > Default
dis.
Absolute Alarm (see par. 12)
a. aL.
Band Alarm (see par. 12)
b. aL.
High Deviation Alarm (see par. 12)
H.d.aL.
Low Deviation Alarm (see par. 12)
L.d.aL.
Absolute Command setpoint Alarm
a.c.aL.
Start Alarm, Active in Run
st.aL.
Cooling
cooL.
Timer 1 Start Alarm
t. 1 .s.a.
Timer 1 End Alarm
t. 1 .e.a.
Timer 1 Warning Expiring
t. 1 .w.e.
Timer 2 Start Alarm
t.2.s.a.
Timer 2 End Alarm
t.2.e.a.
Timer 2 Warning Expiring
t.2.w.e.
Timer 1-2 Start Alarm
t. 1 .2.s.
Timer 1-2 End Alarm
t. 1 .2.e.
Timer 1-2 Warning Expiring
t. 1 .2.w.
42
UR3274U - User manual