6
Boot version
50
Automatic addressing
51
System code comparison
Loading default values:
9999 restore all values
9998 restore all values except for
baud-rate and slave address
500
9997 restore all values except for
slave address
9996 restore all values except for
baud-rate
Process (with tenths of degree for
1000
temperature sensors; digits for
linear sensors)
1001
Setpoint1
1002
Setpoint2
1003
Setpoint3
1004
Setpoint4
1005
Alarm1
1006
Alarm2
1007
Setpoint gradient
Outputs status (0=off, 1=on)
Bit 0 = Q1 relay
1008
Bit 1 = Q2 relay
Bit 2 = SSR
Heating output percentage
1009
(0-10000)
Cooling output percentage
1010
(0-10000)
Alarms status (0=none, 1=active)
1011
Bit0 = Alarm 1
Bit1 = Alarm 2
30
UR3274U - User manual
RO
EEPROM
WO
-
WO
-
WO
0
RO
-
R/W EEPROM
R/W EEPROM
R/W EEPROM
R/W EEPROM
R/W EEPROM
R/W EEPROM
RO
EEPROM
RO
0
RO
0
RO
0
RO
0

Advertisement