Clear Data - GE Multilin PQM Instruction Manual

Power quality meter
Table of Contents

Advertisement

S1 PQM SETUP
4.2.8

Clear Data

4–12
Courtesy of NationalSwitchgear.com
]] SETPOINTS
]] S1 PQM SETUP
] PREFERENCES
]
] CALCULATION
] PARAMETERS
MESSAGE
MESSAGE
] CLEAR DATA
]
FIGURE 4–8: Setpoints Page 1 – PQM Setup / Clear Data
CLEAR ENERGY VALUES: Enter
values subgroup
A1 METERING \ ENERGY . The TIME OF LAST RESET date under the
same subgroup is updated to the current date upon issuing this command.
CLEAR MAX DEMAND VALUES: Enter
demand data under the actual values subgroup
and date associated with each message will be updated to the current date upon
issuing this command.
CLEAR ALL DEMAND VALUES: Enter YES to clear all the power and current demand
data under the actual values subgroup
associated with each message will be updated to the current date upon issuing this
command.
CLEAR MIN/MAX CURRENT VALUES: Enter YES to clear all the min./max current data
under the actual values subgroup
SETPOINT
]] SETPOINTS
]] S2 SYSTEM SETUP
MESSAGE
CLEAR ENERGY
VALUES: NO
CLEAR MAX DEMAND
VALUES: NO
CLEAR ALL DEMAND
VALUES: NO
CLEAR MIN/MAX
CURRENT VALUES: NO
CLEAR MIN/MAX
VOLTAGE VALUES: NO
CLEAR MIN/MAX
POWER VALUES: NO
CLEAR MIN/MAX
FREQUENCY VALUES: NO
CLEAR MAX THD
VALUES: NO
CLEAR PULSE INPUT
VALUES: NO
CLEAR EVENT RECORD:
NO
LOAD FACTORY DEFAULT
SETPOINTS: NO
to clear all the energy used data under the actual
YES
to clear all the max power and current
YES
A1 METERING \ DEMAND . The time
A1 METERING \ DEMAND . The time and date
A1 METERING \ CURRENT . The time and date
PQM POWER QUALITY METER – INSTRUCTION MANUAL
CHAPTER 4: PROGRAMMING
Range: YES, NO
Range: YES, NO
Range: YES, NO
Range: YES, NO
Range: YES, NO
Range: YES, NO
Range: YES, NO
Range: YES, NO
Range: YES, NO
Range: YES, NO
Range: YES, NO