Analog Output Parameter Range - GE Multilin PQM Instruction Manual

Power quality meter
Table of Contents

Advertisement

MODBUS MEMORY MAP
7.3.5
Analog Output
Parameter
Range
Table 7–12: Analog Output Parameter Range for Serial Ports (Sheet 1 of 2)
NO.
ANALOG OUT PARAMETER
0
Not Used
1
Phase A Current
2
Phase B Current
3
Phase C Current
4
Neutral Current
5
Average Phase Current
6
Current Unbalance
7
Voltage Van
8
Voltage Vbn
9
Voltage Vcn
10
Voltage Vab
11
Voltage Vbc
12
Voltage Vca
13
Average Phase Voltage
14
Average Line Voltage
15
Voltage Unbalance
16
Frequency
17
*3 Phase PF
18
3 Phase kW
19
3 Phase kvar
20
3 Phase kVA
21
3 Phase MW
22
3 Phase Mvar
23
3 Phase MVA
24
*Phase A PF
25
Phase A kW
26
Phase A kvar
27
Phase A kVA
28
*Phase B PF
29
Phase B kW
30
Phase B kvar
31
Phase B kVA
32
*Phase C PF
*Due to the fact that –0 and +0 both exist for power factor, the value stored in the PQM serial register is the
opposite of the value shown on the display.
Example: If the range 0.23 lead (–0.23) to 0.35 lag (+0.35) is required, –77 (–100+23)and +65 (100–35) must be
sent.
7–92
Courtesy of NationalSwitchgear.com
CHAPTER 7: MODBUS COMMUNICATIONS
RANGE
STEP
0
0 to 150
0 to 150
0 to 150
0 to 150
0 to 150
0 to 1000
0 to 200
0 to 200
0 to 200
0 to 200
0 to 200
0 to 200
0 to 200
0 to 200
0 to 1000
0 to 7500
–99 to +99
–32500 to +32500
–32500 to +32500
0 to 65400
–32500 to +32500
–32500 to +32500
0 to 65400
–99 to +99
–32500 to +32500
–32500 to +32500
0 to 65400
–99 to +99
–32500 to +32500
–32500 to +32500
0 to 65400
–99 to +99
PQM POWER QUALITY METER – INSTRUCTION MANUAL
UNITS/
DEFAULT
SCALE
0
---
1
%
1
%
1
%
1
%
1
%
1
0.1 x%
1
%
1
%
1
%
1
%
1
%
1
%
1
%
1
%
1
0.1 x%
1
0.01 xHz
1
0.01 xPF
1
kW
1
kvar
1
kVA
1
0.1 xMW
1
0.1 xMvar
1
0.1 xMVA
1
0.01 xPF
1
kW
1
kvar
1
kVA
1
0.01 xPF
1
kW
1
kvar
1
kVA
1
0.01 xPF
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0