Energy - GE Multilin PQM Instruction Manual

Power quality meter
Table of Contents

Advertisement

A1 METERING
5.2.5

Energy

5–14
Courtesy of NationalSwitchgear.com
]] ACTUAL VALUES
]] A1 METERING
MESSAGE
MESSAGE
] ENERGY
]
FIGURE 5–7: Actual Values Page 1 – Metering / Energy
3Φ POS REAL ENERGY: This message displays the positive watthours (in kWh) since the
TIME OF LAST RESET date. Real power in the positive direction will add to this
accumulated value, and real power in the negative direction will add to the negative
watthour value. The setpoint
used to clear this value. The displayed value rolls over to 0 once the value 4294967295
(FFFFFFFFh) has been reached.
3Φ NEG REAL ENERGY: This message displays the negative watthours (in kWh) since the
TIME OF LAST RESET date. Real power in the negative direction will add to this
accumulated value, and real power in the positive direction will add to the positive
ACTUAL
]] ACTUAL VALUES
]] A2 STATUS
MESSAGE
3Φ Φ Φ Φ POS REAL ENERGY
=
32745 kWh
3Φ Φ Φ Φ NEG REAL ENERGY
=
32745 kWh
3Φ Φ Φ Φ POS REACT ENERGY
=
32745 kvarh
3Φ Φ Φ Φ NEG REACT ENERGY
=
32745 kvarh
3Φ Φ Φ Φ APPARENT ENERGY
=
32745 kVAh
REAL ENERGY LAST 24h
=
REAL ENERGY COST =
$12575.34
REAL ENERGY COST =
$125.01 / DAY
TARIFF PERIOD 1 COST
$0.00
TARIFF PERIOD 2 COST
$0.00
TARIFF PERIOD 3 COST
$0.00
TARIFF PERIOD 1 NET
ENERGY:
TARIFF PERIOD 2 NET
ENERGY:
S1 PQM SETUP \ CLEAR DATA \ CLEAR ENERGY VALUES is
PQM POWER QUALITY METER – INSTRUCTION MANUAL
CHAPTER 5: MONITORING
1245 kWh
0
kWh
0
kWh
TARIFF PERIOD 3 NET
ENERGY:
0
kWh
TIME OF LAST RESET:
12:00:00am
01/01/95

Hide quick links: