ProMinent DULCOMETER D1C Type D Operating Instructions Manual page 25

Table of Contents

Advertisement

Complete Operating Menu / Description
Feed forward control
feed forward ctrl.
setting ?
Feed forward control
(flow)
Feed forward control
rated value
Feed forward control
Feed forward effect
Max. additive regulated
value
Standard signal output 1
Access to all setting menus can be blocked with an access code !
only with standard signal output
mA output 1 PS1
setting ?
feed forward ctrl.
Hz / mA
10 Hz
Possible values
Initial value
Increment
as per
none
identity code at
10 Hz
standard signal
500 Hz
0...20 mA
4...20 mA
20 mA
0.01 mA
10 Hz
0.01 Hz
500 Hz
1 Hz
multiplicative
multiplicative
additive
100 %
1 %
mA output 1
measured value
0...20 mA
feed forward ctrl.:
rated value:
10.00 Hz
Lower value
Upper value
0/4 mA
20 mA
0.1 Hz
10 Hz
5 Hz
500 Hz
-500 %
+500 %
Control with standard signal
control
regulated value:
positive cond
negative cond
mA output 1
measured value
0,0 mS/cm
0 mA =
20 mA =
200.0 mS/cm
mA output 1
correction value
0.0 °C
0 mA =
20 mA =
100.0 °C
feed forward ctrl.
effect:
additive
feed forward ctrl.
max. additive
regulated value
100 %
D1C2-cond.-035-GB
Remarks
Signal processing:
Signal < 0,2 mA = No flow
Signal < 4,2 mA = No flow
Depending on signal type.
Maximum limitation of
range used.
Only with additive
regulated value.
mA output 1
regulated value
0%
0 mA =
20 mA =
100%
D1C2-cond.-027-GB
25

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DULCOMETER D1C Type D and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

Dulcometer d1c type w

Table of Contents