Installation Guide
A314.6 example c
Ventilation system with heating, cooling and room temperature control. Analog controlled speed of fans in relation to pressures. Analog
controlled valve (M2) for heat recovery by means of a Fluid battery.
S 1
P
2
Sensor advice:
Sensor S3 must be connected. If not, the fan F1 stops and motorized control valve M1 closes.
S1, S13 and S14 must be connected in order to calculate the recovery efficiency.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value