MENU > Settings > Application
Accum. filter (Accummulation filter)
Circuit
All
The value determines the filtering of the desired flow / duct temperature in
order to change correctly from heating to cooling mode or vice versa.
The set value is an indirect time constant. The resulting time constant is
listed in the examples below.
* See Appendix "Parameter ID overview"
Low value:
Minor dampening.
High value:
Major dampening.
The setting values (examples) give the following approximate time
constants:
Set value (examples):
1:
2:
5:
10:
20:
50:
100:
200:
250:
MENU > Settings > Application
Frost pr. T (frost protection temp.)
Circuit
All
Set the desired flow temperature at temperature sensor S3 to protect the
system against frost (at heating cut-out, total stop etc.).
When the temperature at S3 gets lower than the setting, the motorized
control valve opens gradually.
* See Appendix "Parameter ID overview"
156
DEN-SMT/DK
ECL Comfort 210 / 310, application A214 / A314
1x082
Setting range
Factory setting
*
Resulting time constant:
80 sec
160 sec
~ 7 min
~ 14 min
~ 25 min
~ 1 hour
~ 2 hours
~ 4 hours
~ 5.5 hours
1x093
Setting range
Factory setting
*
Duct / room temp.
*
Actual
Dampened
The setting of 'Accum. filter' prevents unexpected changes between
heating and cooling or changes between heating and passive cooling.
The frost protection temperature can also be set in your favorite
display when the mode selector is in frost protection mode.
*
VI.GU.A2.02
Dead zone (ID no.
11009)
Heating
Cooling