Danfoss ECL Comfort 210 Installation Manual page 163

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
MENU > Settings > Application
Send desired T
Circuit
All
When the controller acts as a slave controller in a master / slave system,
information about the desired flow temperature can be sent to the master
controller via the ECL 485 bus.
* See Appendix "Parameter ID overview"
OFF:
Information about the desired flow temperature is not
sent to the master controller.
ON:
Information about the desired flow temperature is sent
to the master controller.
Danfoss District Energy
ECL Comfort 210 / 310, application A214 / A314
1x500
Factory setting
Setting range
*
In the master controller, 'Demand offset' must be set to a value in order
to react on a desired flow temperature from a slave controller.
*
When the controller acts as a slave, its address must be 1, 2, 3 ... 9 in
order to send the desired temperature to the master (see the section
'Miscellaneous' , 'Several controllers in the same system').
VI.GU.A2.02
DEN-SMT/DK
163

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecl comfort 310

Table of Contents