Danfoss ECL Comfort 210 Installation Manual page 46

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
A314.4 example e
Ventilation system with heating, passive cooling (outside air) and room temperature control. Analog controlled speed of fans in relation
to pressures. Analog controlled valve (M2) for heat recovery by means of a Fluid battery. Control of Night damper P8 for reduced
ventilation during saving periods.
Sensor advice:
Sensor S3 must be connected. If not, the fan F1 stops and motorized control valve M1 closes.
S1, S13 and S14 must be connected in order to calculate the recovery efficiency.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
46
DEN-SMT/DK
ECL Comfort 210 / 310, application A214 / A314
VI.GU.A2.02
ID no.: Recommended
setting:
11676
5 °C
11656
5 °C
11616
0
11616
1
11636
0
11636
1
Danfoss District Energy

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecl comfort 310

Table of Contents