Installation Guide
A214.3 example b
Ventilation system (fan coils) with heating and constant room temperature control
Setting advice:
Set desired room temperature, for example 20 °C.
Set desired balance temperature, for example 35 °C.
If a room temperature sensor is not connected, the desired flow temperature at S3 will correspond to the desired room temperature.
Navigation:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
Danfoss District Energy
ECL Comfort 210 / 310, application A214 / A314
S 1
S 3
X3
S 5
M1
ECL 210 / 310
A1
F1
F1
S 4
VI.GU.A2.02
ID no.: Recommended
setting:
11676
5 °C
11656
5 °C
11616
0
11616
1
11636
0
11636
1
DEN-SMT/DK