Danfoss ECL Comfort 210 Installation Manual page 27

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
ECL Comfort 210 / 310, application A214 / A314
A214.1 example d
Cooling system with constant flow temperature control
S 1
ECL 210 / 310
A1
M2
S 3
F1
Setting advice:
Set desired room temperature, for example 1 °C.
If a room temperature sensor is not connected, the desired flow temperature at S3 will correspond to the desired room temperature.
Set 'Fan cut-in delay' (ID no. 11086 — 'Settings' , 'Fan / acc. control') to 0 seconds.
A214.1 example e
Cooling system in ceiling and constant room temperature control in for example a wine cellar
S 1
ECL 210 / 310
A1
M2
S 3
S 4
F1
Setting advice:
Set desired room temperature, for example 14 °C.
Set desired balance temperature, for example 10 °C.
If a room temperature sensor is not connected, the desired flow temperature at S3 will correspond to the desired room temperature.
Set 'Fan cut-in delay' (ID no. 11086 — 'Settings' , 'Fan / acc. control') to 0 seconds.
Danfoss District Energy
VI.GU.A2.02
DEN-SMT/DK
27