Installation Guide
Heating with room temperature and air pressure control
(continued)
Ventilation during saving period:
A desired reduced pressure can be set.
Room temperature signal must be present
The night damper P8 will open
The fan V2 will operate at reduced speed
The fan V3 is OFF
P2 is OFF
M2 is OFF
Summer cut-out:
When outdoor temperature exceeds a selectable value, the heating
system closes totally.
M1 is 3-point controlled, whereas M2 is 0-10 V controlled.
For a description of alarms, compensation temperature, return
temperature limitation (S5) and frost protection (S6 and S7), please
read the section 'A214 and A314 in general' .