MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
X2
Circuit
All
Definition of which voltage value corresponds to which pressure value.
The voltage (as a 0 - 10 volt signal) comes from a pressure transmitter and is
applied to the relevant input.
This input voltage is converted to display a pressure value (in Pascal).
See also "Pressure" and "X1".
* See Appendix "Parameter ID overview"
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
Pressure
Circuit
All
The actual pressure, measured in Pascal.
A 0 - 10 volt signal comes from a pressure transmitter and is applied to
related input.
This input voltage is converted to the displayed pressure value.
Access to conversion (scale) settings: Push dial.
* See Appendix "Parameter ID overview"
The pressure is measured by means of a 0 - 10 volt signal.
The measured voltage must be converted to a pressure value by
the controller.
The following procedure sets up the conversion:
Push the dial to see the graph and enter the value sets for the 2
input voltages and related pressure values.
Pressure value range: 0 ... 1999 pascal
The factory set voltage values can be changed in the two separate
menus "X1" and "X2".
Typically, the higher the voltage, the higher the displayed pressure.
Danfoss District Energy
ECL Comfort 210 / 310, application A214 / A314
1x407
Setting range
Factory setting
*
Setting range
Factory setting
*
*
= Volt
X
= Pressure
Y
= 'X2'
# 1 #
*
VI.GU.A2.02
DEN-SMT/DK
139