Installing the switch in a 19-inch rack

You can install a 5500 HI switch in a 19-inch rack by using one of the following methods:
Use the front mounting brackets.
Use the front and rear mounting brackets.
NOTE:
If a rack shelf is available, you can put the switch on the rack shelf, slide the switch to an appropriate
position, and attach the switch to the rack with mounting brackets.
Figure 12 Rack-mounting procedure (I)
Figure 13 Rack-mounting procedure (II)

Rack-mounting restrictions and guidelines

Follow the rack-mounting restrictions and guidelines in
that you use.
Table 4 Rack-mounting restrictions and guidelines
Mounting method
Rack-mounting by using front
mounting brackets
Rack-mounting by using front
and rear mounting brackets

Mounting accessory kit

Figure 12
shows the mounting procedure diagram.
Figure 13
Table
Restrictions and guidelines
Only applicable to the 5500-24G-4SFP HI (2 slots), 5500-48G-4SFP HI
(2 slots), 5500-24G-SFP HI (2 slots), and 5500-24G-SFP HI TAA (2 slots)
switches.
Install the front mounting brackets at the port-side or power-side mounting
position as needed.
For the 5500-48G-4SFP HI (2 slots), if you are installing an LSP5GP8P0
(JG314A) interface card, make sure the rack depth is 800 mm (31.50 in)
or 1000 mm (39.37 in).
Only applicable to the 5500-24G-PoE+-4SFP HI (2 slots),
5500-24G-PoE+-4SFP HI TAA (2 slots), 5500-48G-PoE+-4SFP HI (2
slots), and 5500-48G-PoE+-4SFP HI TAA (2 slots) switches.
Install the front mounting brackets at the port-side or power-side mounting
position as needed.
Make sure the rack depth is 800 mm (31.50 in) or 1000 mm (39.37 in).
11
shows the mounting procedure diagram.
4, depending on the mounting accessories